Danfoss Optyma Plus, OP-LPKM084LLP02E
114X3305

Danfoss 114X3305 - Optyma™ Plus, OP-LPKM084LLP02E

  • Segment usage: Low Back Pressure
  • Refrigerants: R404A; R452A; R454C; R448A; R455A; R449A
  • Compressor power supply [V]: 400/3/50
Similar products

Product details

Air flow @ 50Hz [m³/h]5200 m³/h
ApplicationsLBP
ApprovalCE
Capacity controlFixed speed
CE evaluatedYes
China RoHS complianceOut of scope
Compressor High pressure volume (L)0.5
Compressor Low pressure volume (L)4.74 L
Compressor modelLLZ015T4LQ9B
Compressor power supply [V]400/3/50
Condenser Coil Internal Volume [L]1.62 mm³
Condenser typeG7
Condenser volume (L)1.62
Connection typeSolder
Contain batteriesNo
DescriptionOP-LPKM084LLP02E
Electrical codeE
EU RoHS complianceOut of scope
FamilyOptyma™ Plus
Fan blade size [mm]560 mm
Fan cowl/grill typeH3
Fan current @ 50Hz [A]1.6 A
Fan diameter [mm]560 mm
Fan power consumption @ 50Hz [W]140 W
Fan power output @ 50Hz [W]72 W
Fan power supply [V/Ph/Hz]230/1/50
Filter Drier Volume (L)0.35
Frequency [Hz]50 Hz
High value of nominal voltage at 50Hz [V]415 V
HMBP Cooling capacity range [kW] (R513A)Not available for this condition / refrigerant
LBP Cooling capacity [kW] (R452A)3.29 kW
LBP Cooling capacity range [kW] (R452A)1.6 to 3.6 kW
Length [mm]531 mm
Liquid injectionYes
Liquid line connection [in]1/2 in
Low value of nominal voltage at 50Hz [V]380 V
LRA88.5 A
MBP Cooling capacity range [kW] (R449A)Not available for this condition / refrigerant
MCC16.9 A
Min fuse rating [A]20 A
Model numberOP-LPKM084LLP02E
Night operation noise pressure at 10m dB(A)39 dBA
No. of phases (compressor)3
No. of phases (fan)1
Number of fans1
Phase3
Product groupCondensing Units
Product Name DescriptionPackage unit
REACH Candidate List substancesLead (CAS no. 7439-92-1); N,N-dimethylacetamide (CAS no. 127-19-5); Cobalt dichloride (CAS no. 7646-79-9); BIS(2-ETHYLHEXYL) PHTHALATE (CAS no. 117-81-7); Bisphenol A (BPA, CAS no. 80-05-7)
Receiver approvalCE; EAC
Receiver typeVertical
Receiver volume [L]6.2 L
RefrigerantsR404A; R448A; R449A; R452A; R454C; R455A
RLA10.9 A
SCIP dossier product nameOPTYMA P02 G7 J7
Segment usageLow Back Pressure
Sound power @ 50Hz [db(A)]74 dBA
Sound pressure level 50Hz (@1 m distance) [db(A)]63 dBA
Sound pressure level 50Hz (@10 m distance) [db(A)]43 dBA
Suction connection size [in]3/4 in
TechnologyScroll
Total height [mm]965 mm
TypeOptyma™ Plus P02
UK RoHS complianceOut of scope
VersionP02
Voltage 50Hz [V]380 V
Voltage 50Hz [V] [Max]415 V
Volume (L)0.112 L
Width [mm]1441 mm

Technical data

Product typeCondensing Units
Net weight138 kg
Gross weight164 kg
Packed volume73.8 L
EAN5702424595357

Documents

Operating guides, design guides, certificates and CAD drawings for 114X3305 are available on request. Ask for documents →

Request a quote

Price and delivery time, usually within one business day.