Danfoss VACON NXP Liquid Cooled Common DC Bus NXA09206-A0T02WG-A1A2B5D2CQ
132L2397

Danfoss 132L2397 - VACON NXP Liquid Cooled Common DC Bus (972 kW, IP00, 525-690V)

  • Vacon Active Front-End Unit
  • 525 – 690 Vac (640-1100 Vdc), 920 Amp,IP00
  • Alpha-numeric display
  • IEC61800-3 for IT networks
  • No Brake
  • A Slot: 6DI,DO,2AI,1AO,+10Vr,+24V
  • B Slot: 2RO(NO/NC)
  • C Slot: 3RO(NO)
  • D Slot: SysBus(1fiber), CAN-MonBus
  • E Slot: EtherNet/IP
  • Manual: English
  • Frame 64 liquid cooled
Model code:
NXA09206-A0T02WG-A1A2B5D2CQ
Similar products

Product details

Product GroupNXAActive Front-End Unit
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationWLiquid cooling
Mains voltage6-525 – 690 Vac (640-1100 Vdc)
Current0920920 Amp
Control KeypadAAlpha-numeric display
Enclosure0IP00
EMC emission levelsTIEC61800-3 for IT networks
Brake Chopper0No Brake
Electrical Modification2AFE module w/o LCL
Card ModificationsG-FiberConnection+Varnished PCB
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGNONo conduit plate
Option Slot AA16DI,DO,2AI,1AO,+10Vr,+24V
Option Slot BA22RO(NO/NC)
Option Slot CB53RO(NO)
Option Slot DD2SysBus(1fiber), CAN-MonBus
Option Slot ECQEtherNet/IP
Firmware language package+FL22UK,FR,IT,ES,PT;WestEur
Documentation Level+DPAPPaper manuals
Documentation Lang. Preference+DLUKEnglish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+ARFIFF02AFE application NXA,NXI,NXP
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeCH64Frame 64 liquid cooled
Motor Power Low Overload [kW]972
Motor Power High Overload [kW]-
Dimensions WxHxD [mm]746X923X375
Continuous Current (NO) [A]836
Continuous Current (HO) [A]-

Technical data

Motor power972 kW
Mains voltage525 – 690 Vac (640-1100 Vdc)
PhaseThree-phase
Protection ratingIP00
Frame sizeCH64
RFI filterNone (EMC C4)
Brake chopperNo
Control panelAlphanumeric Keypad
Product typeActive Front-End Unit
Continuous output current836 A
Rated current920 A
Power, low overload972 kW
Standard I/O6DI,DO,2AI,1AO,+10Vr,+24V
Height923 mm
Width746 mm
Depth375 mm
Net weight180 kg
Gross weight189 kg
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132L2397 are available on request. Ask for documents →

Other 972 kW variants in VACON® NXP Liquid Cooled Common DC Bus

Request a quote

Price and delivery time, usually within one business day.

We only use your details to answer this request.