Danfoss VACON NXP Air Cooled NXP04606-A0N0USB-A1A2000000
132X7546

Danfoss 132X7546 - VACON NXP Air Cooled (450 kW, IP00, 525-690V)

  • Vacon NXP Frequency Converter
  • 525 – 690 Vac (640-1100 Vdc), 460 Amp,IP00
  • Alpha-numeric display
  • no EMC protection
  • No Brake
  • A Slot: 6DI,DO,2AI,1AO,+10Vr,+24V
  • B Slot: 2RO(NO/NC)
  • C Slot: No board
  • D Slot: No board
  • E Slot: No board
  • Manual: English
  • Frame 11
Model code:
NXP04606-A0N0USB-A1A2000000
Similar products

Product details

Product GroupNXPNXP Frequency Converter
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationSStandard air cooled drive
Mains voltage6-525 – 690 Vac (640-1100 Vdc)
Current0460460 Amp
Control KeypadAAlpha-numeric display
Enclosure0IP00
EMC emission levelsNno EMC protection
Brake Chopper0No Brake
Electrical ModificationU12-pulse No choke Spare unit
Card ModificationsB-Fiber+IntegrControl+varn.PCB
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGNONo conduit plate
Option Slot AA16DI,DO,2AI,1AO,+10Vr,+24V
Option Slot BA22RO(NO/NC)
Option Slot C00No board
Option Slot D00No board
Option Slot E00No board
Firmware language package+FL22UK,FR,IT,ES,PT;WestEur
Documentation Level+DPAPPaper manuals
Documentation Lang. Preference+DLUKEnglish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+A000No Special Application
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeFR11Frame 11
Motor Power Low Overload [kW]450
Motor Power High Overload [kW]355
Dimensions WxHxD [mm]709X1206X503
Continuous Current (NO) [A]460
Continuous Current (HO) [A]385

Technical data

Motor power450 kW
Mains voltage525 – 690 Vac (640-1100 Vdc)
PhaseThree-phase
Protection ratingIP00
Frame sizeFR11
RFI filterNone (EMC C4)
Brake chopperNo
Control panelAlphanumeric Keypad
Product typeNXP Frequency Converter
Continuous output current460 A
Continuous current (high overload)385 A
Rated current460 A
Power, high overload355 kW
Power, low overload450 kW
Standard I/O6DI,DO,2AI,1AO,+10Vr,+24V
Height1206 mm
Width709 mm
Depth503 mm
Net weight210 kg
Gross weight211 kg
EAN5715253225814
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132X7546 are available on request. Ask for documents →

Other 450 kW variants in VACON® NXP Air Cooled

Request a quote

Price and delivery time, usually within one business day.

We only use your details to answer this request.