Danfoss VLT HVAC Drive FC 102 FC-102P1K1T4P55H1XGXXXXSXXXXAXB0CXXXXD0
137X2350

Danfoss 137X2350 - VLT HVAC Drive FC 102 (1.1 kW / 1.5 HP, IP55, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P1K1) 1.1 KW / 1.5 HP,
  • Three phase, 380 - 480 VAC,IP55 / Type12 Backplate
  • (H1) RFI Class A1/B (C1)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: A5
  • No A Option, MCB-109 I/O, RTC Back-up
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102P1K1T4P55H1XGXXXXSXXXXAXB0CXXXXD0
Similar products

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP1K1(P1K1) 1.1 KW / 1.5 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionB0MCB-109 I/O, RTC Back-up
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeA5
Power 110% (NO) [KW]1.1
Height [mm]420,0
Width w/ no C options [mm]242,0
Depth [mm]200,0
Depth with Option A/B [mm]200,0
kVA2.08
Power Loss NO [W]58
Power Loss NO [W]58
Continuous Current (NO) [A]3
Intermittent Current (NO) [A]3.3
Continuous Current (NO) [A]2.7
Intermittent Current (NO) [A]2.97

Technical data

Motor power1.1 kW / 1.5 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeA5
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
FieldbusNone
Product typeFrequency converter
Continuous output current3 A
Continuous current (high line)2.7 A
Intermittent output current3.3 A
Apparent power2.08 kVA
Power loss58 W
Power, normal overload1.1 kW
Height420 mm
Width242 mm
Depth200 mm
Depth with A/B options200 mm
Net weight11.96 kg
Gross weight12.576 kg
EAN5715253809991
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137X2350 are available on request. Ask for documents →

Other 1.1 kW / 1.5 HP variants in VLT® HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

We only use your details to answer this request.