Danfoss Electric expansion valve, ETS 6 - 32
034G5055

Danfoss 034G5055 - Electric expansion valve, ETS 6 - 32

  • Refrigerant temperature [°C] [max]: 70
  • Refrigerant temperature [°F] [max]: 158
  • Inlet size [mm]: 7.94
  • Outlet size [mm]: 7.94
  • Inlet size [in]: 5/16 in
  • Outlet size [in]: 5/16 in
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day
  • Worldwide delivery

Product details

TypeETS 6 - 32
Product groupExpansion valves
Product Name DescriptionElectric expansion valve
Ambient temperature range [°C] [max]70 °C
Ambient temperature range [°C] [min]-30 °C
Ambient temperature range [°F] [max]158 °F
Ambient temperature range [°F] [min]-22 °F
ApprovalCE; CQC; EAC; RoHS; UKCA; UL; UA
CE markYes
China RoHS complianceYes
China RoHS exemption clauseNo
Compatible Danfoss controllersEIM 336; EKE 1A; EKE 1B; EKE 1C
Connection Code(3002:X:8)
Connection materialCopper
Connection typeSolder, ODF
Contains batteriesNo
DirectionAngleway
EU RoHS complianceYes
EU RoHS exemption clauseNo
Flow directionBi-flow
Fluid Group2
Full travel time speed [s] [max]16 s
Full travel time speed [s] [min]6 s
Identical product034G5050
Inlet size [in]5/16 in
Inlet size [mm]7.94
Lubricants compatibilityMO; POE
Manual operation optionAST-G service driver; ETS 6 Manual coil
Max. Working Pressure [bar]47 bar
Max. Working Pressure [psig]681 psig
MaxOPD [bar]28 bar
MaxOPD [psig]406 psig
MOPD[bar/psi]28 bar
Motor typePermanent magnet stepper motor
Orifice size [mm]3.2 mm
Outlet size [in]5/16 in
Outlet size [mm]7.94
Packing formatMulti pack
Parts Program nameETS 6
PED categoryArt. 4, par. 3
Product accessoriesElectric valve accessories
Quantity per packing format10 pc
Rated cap. conditions [IMP]Subcooling=32 °F; Superheat=32 °F; tcond=100 °F; tevap=41 °F
Rated cap. conditions [SI]Subcooling=0 °C; Superheat=0 °C; tcond=38 °C; tevap=5 °C
Rated cap. R404A/R507A [kW]20.3 kW
Rated cap. R404A/R507A [TR]5.77 TR
Rated capacity R134a [kW]22.5 kW
Rated capacity R134a [TR]6.4 TR
Rated capacity R22 [kW]28.8 kW
Rated capacity R22 [TR]8.19 TR
Rated capacity R407C [kW]29.6 kW
Rated capacity R407C [TR]8.42 TR
Rated capacity R410A [kW]33.9 kW
Rated capacity R410A [TR]9.64 TR
REACH Candidate List substancesNo
Refrigerant temperature [°C] [max]70
Refrigerant temperature [°C] [min]-30 °C
Refrigerant temperature [°F] [max]158
Refrigerant temperature [°F] [min]-22 °F
RefrigerantsR1234yf; R134a; R22/R407C; R290; R32; R404A/R507A; R407H; R410A; R448A; R449A; R449B; R452A; R452B; R454A; R454B; R454C; R455A; R463A; R513A
ServiceableNo
Step mode2-phase full step; Half step (recommended); Microstep
Total steps480 (half steps)
UL approved refrigerantsR134a; R22; R404A; R407C; R410A; R448A; R449A; R452A; R507A
UL markYes

Technical data

Product typeExpansion valves
Net weight0.048 kg
Gross weight0.078 kg
Packed volume0.5 L
EAN5702428825498

Documents

Operating guides, design guides, certificates and CAD drawings for 034G5055 are available on request. Ask for documents →

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.