Danfoss VACON NXP Liquid Cooled Common DC Bus NXA11806-A0T02WG-A1A2000000
136H1864

Danfoss 136H1864 - VACON NXP Liquid Cooled Common DC Bus (1372 kW, IP00, 525-690V)

  • Vacon Active Front-End Unit
  • 525 – 690 Vac (640-1100 Vdc), 1180 Amp,IP00
  • Alpha-numeric display
  • IEC61800-3 for IT networks
  • No Brake
  • A Slot: 6DI,DO,2AI,1AO,+10Vr,+24V
  • B Slot: 2RO(NO/NC)
  • C Slot: No board
  • D Slot: No board
  • E Slot: No board
  • Manual: English
  • Frame 64 liquid cooled
Model code:
NXA11806-A0T02WG-A1A2000000
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day
  • Worldwide delivery

Product details

Product GroupNXAActive Front-End Unit
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationWLiquid cooling
Mains voltage6-525 – 690 Vac (640-1100 Vdc)
Current11801180 Amp
Control KeypadAAlpha-numeric display
Enclosure0IP00
EMC emission levelsTIEC61800-3 for IT networks
Brake Chopper0No Brake
Electrical Modification2AFE module w/o LCL
Card ModificationsG-FiberConnection+Varnished PCB
Shipping Package+GSCBCardboard box as Shipping pack
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGNONo conduit plate
Option Slot AA16DI,DO,2AI,1AO,+10Vr,+24V
Option Slot BA22RO(NO/NC)
Option Slot C00No board
Option Slot D00No board
Option Slot E00No board
Firmware language package+FL22UK,FR,IT,ES,PT;WestEur
Documentation Level+DPAPPaper manuals
Documentation Lang. Preference+DLUKEnglish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+ARFIFF02AFE application NXA,NXI,NXP
Parameter SetNONEnone
Motor Parameter Default+LS50Default Motor frequency 50HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeCH64Frame 64 liquid cooled
Motor Power Low Overload [kW]1372
Motor Power High Overload [kW]-
Dimensions WxHxD [mm]746X923X375
Continuous Current (NO) [A]1414
Continuous Current (HO) [A]-

Technical data

Motor power1372 kW
Mains voltage525 – 690 Vac (640-1100 Vdc)
PhaseThree-phase
Protection ratingIP00
Frame sizeCH64
RFI filterNone (EMC C4)
Brake chopperNo
Control panelAlphanumeric Keypad
Product typeActive Front-End Unit
Continuous output current1414 A
Rated current1180 A
Power, low overload1372 kW
Standard I/O6DI,DO,2AI,1AO,+10Vr,+24V
Height923 mm
Width746 mm
Depth375 mm
Net weight180 kg
Gross weight181 kg
EAN5710108683801
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 136H1864 are available on request. Ask for documents →

Other 1372 kW variants in VACON® NXP Liquid Cooled Common DC Bus

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.