114X5722
Danfoss 114X5722 - Optyma™, OP-MCRN030MTA02G
Productos similares
- Productos Danfoss originales
- Garantía del fabricante Danfoss
- Respuesta en un día laborable
Detalles del producto
| Tipo | Optyma™ A02 | |
| Grupo de producto | Condensing Units | |
| Descripción del producto | Bare unit | |
| Air flow @ 50Hz [m³/h] | 1550 m³/h | |
| Applications | MBP | |
| Approval | CE; EAC | |
| CE mark | Sí | |
| Conformidad RoHS China | Fuera del ámbito | |
| Compressor model | MTZ018-5 | |
| Compressor power supply [V] | 230/1/50 | |
| Condenser type | A7 | |
| Connection type | Solder | |
| Contiene baterías | No | |
| Descripción | OP-MCRN030MTA02G | |
| Electrical code | G | |
| Conformidad RoHS UE | Fuera del ámbito | |
| Family | Optyma™ | |
| Fan blade size [mm] | 350 mm | |
| Fan cowl/grill type | Cowl | |
| Fan current @ 50Hz [A] | 0.35 A | |
| Fan power consumption @ 50Hz [W] | 75 W | |
| Fan power output @ 50Hz [W] | 13 W | |
| Fan power supply [V/Ph/Hz] | 230/1/50 | |
| Fan voltage @ 50Hz (max) [V] [Max] | 230 V | |
| Fan voltage @ 50Hz (max) [V] [Min] | 207 V | |
| Frequency [Hz] | 50 Hz | |
| High value of nominal voltage at 60Hz [V] | 253 V | |
| HMBP Cooling capacity [kW] (R513A/R134a) | 1.44 kW | |
| HMBP Cooling capacity range [kW] (R513A/R134a) | 1.3 to 3.7 kW | |
| Dentro del ámbito RAEE | No | |
| LBP Cooling capacity range [kW] (R452A) | Not available for this condition / refrigerant | |
| Length [mm] | 650 mm | |
| Liquid line connection [in] | 3/8 in | |
| Low value of voltage range at 60Hz [V] | 207 V | |
| LRA | 40 A | |
| MBP Cooling capacity [kW] (R449A) | 2.42 kW | |
| MBP Cooling capacity range [kW] (R22) | Not available for this condition / refrigerant | |
| MBP Cooling capacity range [kW] (R449A) | 1.5 to 3.7 kW | |
| MCC | 10.43 A | |
| Model number | OP-MCRN030MTA02G | |
| No. of phases (compressor) | 1 | |
| No. of phases (fan) | 1 | |
| Number of fans | 1 | |
| Fases | 1 | |
| REACH Candidate List substances | Lead (CAS no. 7439-92-1); N,N-dimethylacetamide (CAS no. 127-19-5) | |
| Receiver approval | CE | |
| Receiver volume [L] | 3 L | |
| Refrigerants | R404A; R452A; R507A; R134a; R407A; R407C; R407F; R448A; R449A; R513A | |
| SCIP dossier product name | Optyma A02 A7 | |
| Segment usage | Medium Back Pressure | |
| Sound power @ 50Hz [db(A)] | 76 dBA | |
| Sound pressure level 50Hz (@10 m distance) [db(A)] | 45 dBA | |
| Speed Platform | Fixed-speed | |
| Suction connection size [in] | 1/2 in | |
| Total height [mm] | 545 mm | |
| Version | A02 | |
| VersionDescription | A02 : Optyma with receiver + stop valve + universal pressure switch (KP-17WB) + flexible hoses + electrical box | |
| Voltage 50Hz [V] | 207 V | |
| Voltage 50Hz [V] [Max] | 253 V | |
| Width [mm] | 630 mm |
Datos técnicos
| Tipo de producto | Condensing Units | |
| Peso neto | 62.427 kg | |
| Peso bruto | 64 kg | |
| Volumen embalado | 382.1 L | |
| EAN | 5702428563147 | |
Documentos
Operating guides, design guides, certificates and CAD drawings for 114X5722 are available on request. Solicitar documentos →