Danfoss Condensing pressure regulator, KVR 15
034L0097

Danfoss 034L0097 - Condensing pressure regulator, KVR 15

  • Inlet size [mm]: 16
  • Outlet size [mm]: 16
  • Inlet connection type: Solder, ODF
  • Outlet connection type: Solder, ODF
  • Max. Working Pressure [bar]: 28
Produits similaires
  • Produits Danfoss d’origine
  • Garantie constructeur Danfoss
  • Réponse sous un jour ouvré

Détails du produit

TypeKVR 15
Groupe de produitsPress. and temp. regul. valves
Description du produitCondensing pressure regulator
ApprovalC UL US LISTED; EAC; RoHS; RoHS China; UA
Approval file nameREFRIGERANT VALVE 53R0
Conformité RoHS ChineOui
Connection Code(3001:X:16); (3002:X:16)
Contient des pilesNon
Customer part number00A393
EquipmentSchrader valve access port
Conformité RoHS UEOui
EU RoHS exemption clauseNon
Factory setting [bar]10 bar
Factory setting [psig]145 psig
Flow direction indicatorEngraved 1-way arrow
Identical product034L1097
Inlet connection typeSolder, ODF
Inlet size [in]5/8 in
Inlet size [mm]16
Lubricants compatibilityOilfree applications
Max. test pressure [bar]31 bar
Max. test pressure [psig]450 psig
Max. Working Pressure [bar]28
Max. Working Pressure [psig]406 psig
Medium temperature range [°C] [max]130 °C
Medium temperature range [°C] [min]-45 °C
Medium temperature range [°F] [max]266 °F
Medium temperature range [°F] [min]-49 °F
Oil free refrigerantsR1234ze(E); R513A
Other RoHS documentationEAEU RoHS
Outlet connection typeSolder, ODF
Outlet size [in]5/8 in
Outlet size [mm]16
P band max. [bar]6.2 bar
P band max. [psi]90 psi
ConditionnementLot
Product accessoriesNon
Quantité par conditionnement12 pc
Rated cap. conditions [IMP]Delta p hotgas=6 psi; Delta p liquid=3 psi; tcond=110 °F; tevap=40 °F
Rated cap. conditions [SI]Delta p hotgas=0.4 bar; Delta p liquid=0.2 bar; Offset=3 bar; tcond=30 °C; tevap=-10 °C
Rated cap. R134a, Hot gas [kW]11.5 kW
Rated cap. R134a, Hot gas [TR]3.03 TR
Rated cap. R22, Hot gas [kW]13.2 kW
Rated cap. R22, Hot gas [TR]4.13 TR
Rated cap. R404A/R507A [kW]36.6 kW
Rated cap. R404A/R507A [TR]8.2 TR
Rated cap. R407C, Hot gas [kW]14.3 kW
Rated cap. R407C, Hot gas [TR]4.5 TR
Rated cap.R404A/R507,Hot gas[k12 kW
Rated cap.R404A/R507,Hot gas[T3.27 TR
Rated capacity R134a [kW]47.3 kW
Rated capacity R134a [TR]11.8 TR
Rated capacity R22 [kW]50.4 kW
Rated capacity R22 [TR]12.7 TR
Rated capacity R407C [kW]54.4 kW
Rated capacity R407C [TR]13.8 TR
REACH Candidate List substancesLead (CAS no. 7439-92-1)
RefrigerantsR1234yf; R1234ze(E); R1270; R134a; R22; R290; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R448A; R449A; R449B; R450A; R452A; R454A; R454C; R455A; R507A; R513A; R515B; R516A; R600; R600a
Regulation range [bar] [max]17.5 bar
Regulation range [bar] [min]5 bar
Regulation range [psig] Pe [max]254 psig
Regulation range [psig] Pe [min]73 psig
SCIP dossier product nameKV
ServiceableKV valves spare parts
UL approved refrigerantsR134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R448A; R449A; R449B; R450A; R452A; R507A; R513A; R515B
UL markOui

Données techniques

Type de produitPress. and temp. regul. valves
Poids net0.355 kg
Poids brut0.392 kg
Volume emballé1.2 L
EAN5702428411585

Documents

Operating guides, design guides, certificates and CAD drawings for 034L0097 are available on request. Demander les documents →

Demander un devis

Prix et délai de livraison, en général sous un jour ouvré.

Danfoss d’origine · Garantie constructeur · Livraison mondiale

Nous utilisons vos données uniquement pour répondre à cette demande. Voir notre politique de confidentialité.