Danfoss VLT AutomationDrive FC 302 FC-302P45KT5E20H2XGXXXXSXXXXA0B2CXXXXD0
131G2490

Danfoss 131G2490 - VLT AutomationDrive FC 302 (45 kW / 60 HP, IP20, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P45K) 45 KW / 60 HP,
  • Three phase, 380 - 500 VAC,(E20) IP20 / Chassis
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: C3
  • PROFIBUS DP MCA 101, MCB-112 PTC Therm. Card
  • No C1 option, MCB-107 24V DC backup
  • ATEX: II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db]
Model code:
FC-302P45KT5E20H2XGXXXXSXXXXA0B2CXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP45K(P45K) 45 KW / 60 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE20(E20) IP20 / Chassis
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionB2MCB-112 PTC Therm. Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeC3
Power 150% (HO) [KW]45
Power 110% (NO) [KW]55
Height [mm]550,0
Width w/ no C options [mm]308,0
Depth [mm]333,0
Depth with Option A/B [mm]333,0
kVA62.4
Power Loss NO [W]1083
Power Loss HO [W]891
Continuous Current (NO) [A]106
Intermittent Current (NO) [A]117
Continuous Current (NO) [A]105
Intermittent Current (NO) [A]116
Continuous Current (HO) [A]90
Intermittent Current (HO) [A]135
Continuous Current (HO) [A]80
Intermittent Current (HO) [A]120
ATEX Marking 1ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2db Gb] / II (2) D [Ex tb Db]

Technical data

Motor power45 kW / 60 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP20 / Chassis
Frame sizeC3
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current106 A
Continuous current (high line)105 A
Intermittent output current117 A
Continuous current (high overload)90 A
Apparent power62.4 kVA
Power loss1083 W
Power, normal overload55 kW
Power, high overload45 kW
Height550 mm
Width308 mm
Depth333 mm
Depth with A/B options333 mm
Net weight33.54 kg
Gross weight36.39 kg
Packed volume151 L
EAN5710107205400
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 131G2490 are available on request. Ask for documents →

Other 45 kW / 60 HP variants in VLT AutomationDrive FC 302

Request a quote