131N6518
Danfoss 131N6518 - VLT HVAC Drive FC 102 (45 kW / 60 HP, IP20, 525-600V)
- Frequency Converter
- VLT® HVAC Drive FC-102
- (P45K) 45 KW / 60 HP,
- Three phase, 525 - 600 VAC,(E20) IP20 / Chassis
- No RFI Filter
- No brake chopper
- Graphical Loc. Cont. Panel
- Coated PCB, No Mains Option
- Latest release std. SW.
- Frame: C3
- No A Option, MCB-109 I/O, RTC Back-up
- No C1 option, No D option
Model code:
FC-102P45KT6E20HXXGCXXXSXXXXAXB0CXXXXDX
FC-102P45KT6E20HXXGCXXXSXXXXAXB0CXXXXDX
Similar products
- Genuine Danfoss products
- Danfoss manufacturer warranty
- Reply within one business day
Product details
| Product Group | FC- | VLT® HVAC Drive FC- |
| Series | 102 | |
| Power Rating | P45K | (P45K) 45 KW / 60 HP |
| Phase | T | Three phase |
| Mains Voltage | 6 | 525 - 600 VAC |
| Enclosure | E20 | (E20) IP20 / Chassis |
| RFI Filter | HX | No RFI Filter |
| Brake - Safe Stop | X | No brake chopper |
| LCP | G | Graphical Loc. Cont. Panel |
| Coating PCB | C | Coated PCB |
| Mains Option | X | No Mains Option |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| A Option | AX | No A Option |
| B Option | B0 | MCB-109 I/O, RTC Back-up |
| C0 Option MCO | CX | No C0 option |
| C1 Option | X | No C1 option |
| C Option Software | XX | No software option |
| D Option | DX | No D option |
| Frame Size | C3 | |
| Power 110% (NO) [KW] | 45 | |
| Height [mm] | 550,0 | |
| Width w/ no C options [mm] | 308,0 | |
| Depth [mm] | 333,0 | |
| Depth with Option A/B [mm] | 333,0 | |
| kVA | 61.7 | |
| Power Loss NO [W] | 850 | |
| Continuous Current (NO) [A] | 65 | |
| Intermittent Current (NO) [A] | 71.5 | |
| Continuous Current (NO) [A] | 62 | |
| Intermittent Current (NO) [A] | 68.2 |
Technical data
| Motor power | 45 kW / 60 HP | |
| Mains voltage | 525 - 600 VAC | |
| Phase | Three-phase | |
| Protection rating | IP20 / Chassis | |
| Frame size | C3 | |
| RFI filter | None | |
| Brake chopper | No | |
| Control panel | Graphical LCP | |
| PCB coating | Coated PCB | |
| Mains option | None | |
| Fieldbus | None | |
| Product type | Frequency converter | |
| Continuous output current | 65 A | |
| Continuous current (high line) | 62 A | |
| Intermittent output current | 71.5 A | |
| Apparent power | 61.7 kVA | |
| Power loss | 850 W | |
| Power, normal overload | 45 kW | |
| Height | 550 mm | |
| Width | 308 mm | |
| Depth | 333 mm | |
| Depth with A/B options | 333 mm | |
| Net weight | 33.07 kg | |
| Gross weight | 35.92 kg | |
| Packed volume | 188.2 L | |
| EAN | 5702427874855 | |
| ECCN (EU) | Y901 | |
| ECCN (US) | 3A999.a | |
Documents
Operating guides, design guides, certificates and CAD drawings for 131N6518 are available on request. Ask for documents →
Other 45 kW / 60 HP variants in VLT HVAC Drive FC 102
- 131F0617 IP20 · None · C3
- 137H2350 IP20 · None · C3
- 134F4414 IP20 · None · C3
- 132L2412 IP20 · None · C3
- 137N0051 IP20 · None · C3
- 131N4281 IP20 · None · C3
- 134N3176 IP20 · None · C3
- 134F7437 IP20 · None · C3
- 131H9890 IP20 · None · C3
- 131G8475 IP20 · None · C3
- 131N3904 IP20 · None · C3
- 131N3905 IP20 · None · C3
- 135U8960 IP20 · None · C3
- 134H8012 IP20 · None · C3
- 136G9702 IP20 · None · C3
- 134H3851 IP20 · None · C3
- 131N1826 IP20 · None · C3
- 132X9748 IP21 · None · C1
- 131X5987 IP21 · None · C1
- 132N4786 IP21 · None · C1
- 131U7272 IP21 · None · C1
- 134U0800 IP21 · None · C1
- 131H9020 IP21 · None · C1
- 131G8476 IP21 · None · C1