Danfoss VLT AutomationDrive FC 302 FC-302P710T7E21H2XGCAXMSXXXXA0BRCXRXXD0
131U4169

Danfoss 131U4169 - VLT AutomationDrive FC 302 (710 kW / 1000 HP, IP21, 525-690V)

  • Frequency converter
  • NB: F-frame platform available until December 31, 2025
  • VLT® AutomationDrive FC-302
  • (P710) 710 KW / 1000 HP, Specific Ratings: 560kW@525-550V, 750HP@575V, 710kW@690V
  • Three phase, 525 - 690 VAC *,IP21 / Type 1
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse + Loadsharing
  • Latest release std. SW.
  • Frame: F1
  • PROFIBUS DP MCA 101, MCB-102 Encoder Option
  • MCB-113 Ext. Relay Card, MCB-107 24V DC backup
Model code:
FC-302P710T7E21H2XGCAXMSXXXXA0BRCXRXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP710(P710) 710 KW / 1000 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE21IP21 / Type 1
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionAFuse + Loadsharing
Adaptation AXStandard Cable Entries
Adaptation BMExt Temp Mon+F Com MotTerm
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBRMCB-102 Encoder Option
C0 Option MCOCXNo C0 option
C1 OptionRMCB-113 Ext. Relay Card
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeF1
Power 150% (HO) [KW]710
Power 110% (NO) [KW]800
Height [mm]2204,0
Width w/ no C options [mm]1400,0
Depth [mm]606,0
Depth with Option A/B [mm]606,0
kVA872
Power Loss NO [W]10872
Power Loss NO [W]11304
Power Loss HO [W]9165
Power Loss HO [W]9537
Continuous Current (NO) [A]889
Intermittent Current (NO) [A]978
Continuous Current (NO) [A]850
Intermittent Current (NO) [A]935
Continuous Current (HO) [A]763
Intermittent Current (HO) [A]1144
Continuous Current (HO) [A]730
Intermittent Current (HO) [A]1095
Power Rating at 525-550V560kW
Power Rating at 575V750HP
Power Rating at 690V710kW

Technical data

Motor power710 kW / 1000 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeF1
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionFuse + Loadsharing
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current889 A
Continuous current (high line)850 A
Intermittent output current978 A
Continuous current (high overload)763 A
Apparent power872 kVA
Power loss10872 W
Power, normal overload800 kW
Power, high overload710 kW
Height2204 mm
Width1400 mm
Depth606 mm
Depth with A/B options606 mm
Net weight1004 kg
Gross weight1004.3 kg
EAN5702427954090
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 131U4169 are available on request. Ask for documents →

Other 710 kW / 1000 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.