Danfoss VLT AutomationDrive FC 302 FC-302P55KT7E21H4XGCDXXSXXXXA0BXCXXXXDX
131X6881

Danfoss 131X6881 - VLT AutomationDrive FC 302 (55 kW / 75 HP, IP21, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P55K) 55 KW / 75 HP, Specific Ratings: 45kW@525-550V, 60HP@575V, 55kW@690V
  • Three phase, 525 - 690 VAC *,IP21 / Type 1
  • RFI class A1 (C2)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Loadsharing
  • Latest release std. SW.
  • Frame: C2
  • PROFIBUS DP MCA 101, No B Option
  • No C1 option, No D option
Model code:
FC-302P55KT7E21H4XGCDXXSXXXXA0BXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP55K(P55K) 55 KW / 75 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE21IP21 / Type 1
RFI FilterH4RFI class A1 (C2)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionDLoadsharing
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 150% (HO) [KW]55
Power 110% (NO) [KW]75
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA74.1
Power Loss NO [W]1500
Power Loss HO [W]1100
Continuous Current (NO) [A]87
Intermittent Current (NO) [A]95.7
Continuous Current (NO) [A]83
Intermittent Current (NO) [A]91.3
Continuous Current (HO) [A]65
Intermittent Current (HO) [A]97.5
Continuous Current (HO) [A]62
Intermittent Current (HO) [A]93
Power Rating at 525-550V45kW
Power Rating at 575V60HP
Power Rating at 690V55kW

Technical data

Motor power55 kW / 75 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeC2
RFI filterClass A1 (EMC C2)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionLoadsharing
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current87 A
Continuous current (high line)83 A
Intermittent output current95.7 A
Continuous current (high overload)65 A
Apparent power74.1 kVA
Power loss1500 W
Power, normal overload75 kW
Power, high overload55 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight57.59 kg
Gross weight60.93 kg
Packed volume232.7 L
EAN5710107259847
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 131X6881 are available on request. Ask for documents →

Other 55 kW / 75 HP variants in VLT AutomationDrive FC 302

Request a quote