Danfoss VLT HVAC Drive FC 102 FC-102P15KT4E55H1XGC1XXSXXXXAXBPCXXXXD0
131Z9716

Danfoss 131Z9716 - VLT HVAC Drive FC 102 (15 kW / 20 HP, IP55, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P15K) 15 KW / 20 HP,
  • Three phase, 380 - 480 VAC,IP55 / Type 12
  • (H1) RFI Class A1/B (C1)
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: B1
  • No A Option, MCB-105 Relay Card
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102P15KT4E55H1XGC1XXSXXXXAXBPCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP15K(P15K) 15 KW / 20 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE55IP55 / Type 12
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBPMCB-105 Relay Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeB1
Power 110% (NO) [KW]15
Height [mm]494,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
kVA22.2
Power Loss NO [W]392
Continuous Current (NO) [A]32
Intermittent Current (NO) [A]35.2
Continuous Current (NO) [A]27
Intermittent Current (NO) [A]29.7

Technical data

Motor power15 kW / 20 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12
Frame sizeB1
RFI filterClass A1/B (EMC C1)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
FieldbusNone
Product typeFrequency converter
Continuous output current32 A
Continuous current (high line)27 A
Intermittent output current35.2 A
Apparent power22.2 kVA
Power loss392 W
Power, normal overload15 kW
Height494 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight21.12 kg
Gross weight24.74 kg
EAN5710107394265
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 131Z9716 are available on request. Ask for documents →

Other 15 kW / 20 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.