Danfoss VLT AutomationDrive FC 302 FC-302P11KT2P55H2BGXXXXSXXXXAXBXCXXXXDX
132H2030

Danfoss 132H2030 - VLT AutomationDrive FC 302 (11 kW / 15 HP, IP55, 200-240V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P11K) 11 KW / 15 HP,
  • Three phase, 200 - 240 VAC,IP55 / Type12 Backplate
  • RFI Filter
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: B2
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-302P11KT2P55H2BGXXXXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP11K(P11K) 11 KW / 15 HP
PhaseTThree phase
Mains Voltage2200 - 240 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH2RFI Filter
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeB2
Power 160% (HO) [KW]11
Power 110% (NO) [KW]15
Height [mm]664,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
kVA16.6
Power Loss NO [W]602
Power Loss HO [W]463
Continuous Current (NO) [A]59.4
Intermittent Current (NO) [A]65.3
Continuous Current (HO) [A]46.2
Intermittent Current (HO) [A]73.9

Technical data

Motor power11 kW / 15 HP
Mains voltage200 - 240 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeB2
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
FieldbusNone
Product typeFrequency converter
Continuous output current59.4 A
Intermittent output current65.3 A
Continuous current (high overload)46.2 A
Apparent power16.6 kVA
Power loss602 W
Power, normal overload15 kW
Power, high overload11 kW
Height664 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight29.3 kg
Gross weight32.86 kg
Packed volume105.7 L
EAN5714853307593
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132H2030 are available on request. Ask for documents →

Other 11 kW / 15 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.