Danfoss VLT AutomationDrive FC 302 FC-302P1K5T5Y55H1BGC1OXSXXXXAXBXCXXXXDX
132H4016

Danfoss 132H4016 - VLT AutomationDrive FC 302 (1.5 kW / 2 HP, IP55, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P1K5) 1.5 KW / 2.0 HP,
  • Three phase, 380 - 500 VAC,IP55 / Type 12 Backplate
  • (H1) RFI Class A1/B (C1)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: A4
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-302P1K5T5Y55H1BGC1OXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP1K5(P1K5) 1.5 KW / 2.0 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureY55IP55 / Type 12 Backplate
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AOMetric thread cable entry
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeA4
Power 160% (HO) [KW]1.5
Height [mm]391,0
Width w/ no C options [mm]200,0
Depth [mm]177,0
Depth with Option A/B [mm]177,0
kVA2.84
Power Loss HO [W]62
Continuous Current (HO) [A]4.1
Intermittent Current (HO) [A]6.56
Continuous Current (HO) [A]3.4
Intermittent Current (HO) [A]5.44

Technical data

Motor power1.5 kW / 2 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12 Backplate
Frame sizeA4
RFI filterClass A1/B (EMC C1)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
FieldbusNone
Product typeFrequency converter
Continuous output current4.1 A
Intermittent output current6.56 A
Apparent power2.84 kVA
Power loss62 W
Power, high overload1.5 kW
Height391 mm
Width200 mm
Depth177 mm
Depth with A/B options177 mm
Net weight8.68 kg
Gross weight9.42 kg
Packed volume52.4 L
EAN5714853330171
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132H4016 are available on request. Ask for documents →

Other 1.5 kW / 2 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.