Danfoss VLT AutomationDrive FC 302 FC-302N500T7E5MH2XGC3XXSXXXXA4B2CXXXXD0
132H6368

Danfoss 132H6368 - VLT AutomationDrive FC 302 (500 kW / 650 HP, IP54, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (N500) 500 KW / 650 HP, Specific Ratings: 400kW@525-550V, 500HP@575V, 500kW@690V
  • Three phase, 525 - 690 VAC *,IP54/Type 12+main shield
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: E1H
  • DeviceNet MCA 104, MCB-112 PTC Therm. Card
  • No C1 option, MCB-107 24V DC backup
  • ATEX: II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db]
Model code:
FC-302N500T7E5MH2XGC3XXSXXXXA4B2CXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingN500(N500) 500 KW / 650 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE5MIP54/Type 12+main shield
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA4DeviceNet MCA 104
B OptionB2MCB-112 PTC Therm. Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeE1H
Power 150% (HO) [KW]500
Power 110% (NO) [KW]560
Height [mm]2000,0
Width w/ no C options [mm]600,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
kVA598
Power Loss NO [W]8076
Power Loss NO [W]7852
Power Loss HO [W]6833
Power Loss HO [W]6678
Continuous Current (NO) [A]596
Intermittent Current (NO) [A]656
Continuous Current (NO) [A]570
Intermittent Current (NO) [A]627
Continuous Current (HO) [A]523
Intermittent Current (HO) [A]784
Continuous Current (HO) [A]500
Intermittent Current (HO) [A]750
ATEX Marking 1ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2db Gb] / II (2) D [Ex tb Db]
Power Rating at 525-550V400kW
Power Rating at 575V500HP
Power Rating at 690V500kW

Technical data

Motor power500 kW / 650 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeE1H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
FieldbusDeviceNet MCA 104
Product typeFrequency converter
Continuous output current596 A
Continuous current (high line)570 A
Intermittent output current656 A
Continuous current (high overload)523 A
Apparent power598 kVA
Power loss8076 W
Power, normal overload560 kW
Power, high overload500 kW
Height2000 mm
Width600 mm
Depth510 mm
Depth with A/B options510 mm
Net weight258 kg
Gross weight298 kg
EAN5714853354610
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132H6368 are available on request. Ask for documents →

Other 500 kW / 650 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.