Danfoss VLT HVAC Drive FC 102 FC-102N110T4E54H2TGR7XXSXXXXANB2CXXXXDX
132L5546

Danfoss 132L5546 - VLT HVAC Drive FC 102 (110 kW / 150 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N110) 110 KW / 150 HP,
  • Three phase, 380 - 480 VAC,(E54) IP54 / Type 12
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB 3C3 + Ruggedised, Fuse
  • Latest release std. SW.
  • Frame: D1H
  • EtherNet/IP MCA 121, MCB-112 PTC Therm. Card
  • No C1 option, No D option
  • ATEX: II (2) G [Ex eb Gb] [Ex db Gb] / II (2) D [Ex tb Db]
Model code:
FC-102N110T4E54H2TGR7XXSXXXXANB2CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN110(N110) 110 KW / 150 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBRCoated PCB 3C3 + Ruggedised
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionANEtherNet/IP MCA 121
B OptionB2MCB-112 PTC Therm. Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD1H
Power 110% (NO) [KW]110
Height [mm]901,0
Width w/ no C options [mm]325,0
Depth [mm]378,0
Depth with Option A/B [mm]378,0
kVA147
Power Loss NO [W]2555
Power Loss NO [W]2257
Continuous Current (NO) [A]212
Intermittent Current (NO) [A]233
Continuous Current (NO) [A]190
Intermittent Current (NO) [A]209
ATEX Marking 1ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2db Gb] / II (2) D [Ex tb Db]

Technical data

Motor power110 kW / 150 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeD1H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB 3C3 + Ruggedised
Mains optionIntegrated Fuse
FieldbusEtherNet/IP MCA 121
Product typeFrequency converter
Continuous output current212 A
Continuous current (high line)190 A
Intermittent output current233 A
Apparent power147 kVA
Power loss2555 W
Power, normal overload110 kW
Height901 mm
Width325 mm
Depth378 mm
Depth with A/B options378 mm
Net weight62 kg
Gross weight62.3 kg
EAN5714853450091
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132L5546 are available on request. Ask for documents →

Other 110 kW / 150 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.