132L8075

Danfoss 132L8075 - VLT AutomationDrive FC 302 (160 kW / 250 HP, IP21, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (N160) 160 KW / 250 HP,
  • Three phase, 380 - 500 VAC,IP21 / Type 1
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Condition Based Monitoring CBM
  • Frame: D2H
  • PROFINET MCA 120, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-302N160T5E21H2XGC7XQLX1XXALBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingN160(N160) 160 KW / 250 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE21IP21 / Type 1
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BQHeat-sink access
Software ReleaseLX1XCondition Based Monitoring CBM
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeD2H
Power 150% (HO) [KW]160
Power 110% (NO) [KW]200
Height [mm]1060,0
Width w/ no C options [mm]420,0
Depth [mm]378,0
Depth with Option A/B [mm]378,0
kVA218
Continuous Current (NO) [A]395
Intermittent Current (NO) [A]435
Continuous Current (NO) [A]361
Intermittent Current (NO) [A]397
Continuous Current (HO) [A]315
Intermittent Current (HO) [A]472
Continuous Current (HO) [A]302
Intermittent Current (HO) [A]453

Technical data

Motor power160 kW / 250 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeD2H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current395 A
Continuous current (high line)361 A
Intermittent output current435 A
Continuous current (high overload)315 A
Apparent power218 kVA
Power, normal overload200 kW
Power, high overload160 kW
Height1060 mm
Width420 mm
Depth378 mm
Depth with A/B options378 mm
Net weight125 kg
Gross weight125.3 kg
EAN5714853896899
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132L8075 are available on request. Ask for documents →

Other 160 kW / 250 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.