Danfoss VLT AQUA Drive FC 202 FC-202P18KT4P55H1BGC1OXLX1XXANBXCXXXXD0
132N0457

Danfoss 132N0457 - VLT AQUA Drive FC 202 (18.5 kW / 25 HP, IP55, 380-480V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P18K) 18.5 KW / 25 HP,
  • Three phase, 380 - 480 VAC,IP55 / Type12 Backplate
  • (H1) RFI Class A1/B (C1)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Condition Based Monitoring CBM
  • Frame: B1
  • EtherNet/IP MCA 121, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-202P18KT4P55H1BGC1OXLX1XXANBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP18K(P18K) 18.5 KW / 25 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AOMetric thread cable entry
Adaptation BXNo adaptation
Software ReleaseLX1XCondition Based Monitoring CBM
Software Language PackXStandard Language Pack
A OptionANEtherNet/IP MCA 121
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeB1
Power 160% (HO) [KW]15
Power 110% (NO) [KW]18.5
Height [mm]494,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
kVA26
Power Loss NO [W]465
Power Loss HO [W]379
Continuous Current (NO) [A]37.5
Intermittent Current (NO) [A]41.2
Continuous Current (NO) [A]34
Intermittent Current (NO) [A]37.4
Continuous Current (HO) [A]32
Intermittent Current (HO) [A]51.2
Continuous Current (HO) [A]27
Intermittent Current (HO) [A]43.2

Technical data

Motor power18.5 kW / 25 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeB1
RFI filterClass A1/B (EMC C1)
Brake chopperYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
FieldbusEtherNet/IP MCA 121
Product typeFrequency converter
Continuous output current37.5 A
Continuous current (high line)34 A
Intermittent output current41.2 A
Continuous current (high overload)32 A
Apparent power26 kVA
Power loss465 W
Power, normal overload18.5 kW
Power, high overload15 kW
Height494 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight23 kg
Gross weight26.62 kg
Packed volume105.7 L
EAN5715253042466
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132N0457 are available on request. Ask for documents →

Other 18.5 kW / 25 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.