Danfoss VLT AutomationDrive FC 302 FC-302P2K2T5E66H1BGC1XXSXXXXAQBKCXXXXD0
132N0948

Danfoss 132N0948 - VLT AutomationDrive FC 302 (2.2 kW / 3 HP, IP66, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P2K2) 2.2 KW / 3.0 HP,
  • Three phase, 380 - 500 VAC,(E66) IP66 / NEMA 4X
  • (H1) RFI Class A1/B (C1)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: A5
  • Modbus TCP MCA 122, MCB-101 General purp. I/O
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-302P2K2T5E66H1BGC1XXSXXXXAQBKCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP2K2(P2K2) 2.2 KW / 3.0 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE66(E66) IP66 / NEMA 4X
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAQModbus TCP MCA 122
B OptionBKMCB-101 General purp. I/O
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeA5
Power 160% (HO) [KW]2.2
Height [mm]420,0
Width w/ no C options [mm]242,0
Depth [mm]200,0
Depth with Option A/B [mm]200,0
kVA3.88
Power Loss HO [W]88
Continuous Current (HO) [A]5.6
Intermittent Current (HO) [A]8.96
Continuous Current (HO) [A]4.8
Intermittent Current (HO) [A]7.68

Technical data

Motor power2.2 kW / 3 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP66 / NEMA 4X
Frame sizeA5
RFI filterClass A1/B (EMC C1)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
FieldbusModbus TCP MCA 122
Product typeFrequency converter
Continuous output current5.6 A
Intermittent output current8.96 A
Apparent power3.88 kVA
Power loss88 W
Power, high overload2.2 kW
Height420 mm
Width242 mm
Depth200 mm
Depth with A/B options200 mm
Net weight12.05 kg
Gross weight12.67 kg
Packed volume52.4 L
EAN5715253047485
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132N0948 are available on request. Ask for documents →

Other 2.2 kW / 3 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.