Danfoss VLT HVAC Drive FC 102 FC-102P22KT4P21H2XGC3XXSXXXXAXBXCXXXXD0
132X4810

Danfoss 132X4810 - VLT HVAC Drive FC 102 (22 kW / 30 HP, IP21, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P22K) 22 KW / 30 HP,
  • Three phase, 380 - 480 VAC,IP21 / Type 1 Backplate
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: B2
  • No A Option, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102P22KT4P21H2XGC3XXSXXXXAXBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP22K(P22K) 22 KW / 30 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP21IP21 / Type 1 Backplate
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeB2
Power 110% (NO) [KW]22
Height [mm]664,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
kVA30.5
Power Loss NO [W]525
Continuous Current (NO) [A]44
Intermittent Current (NO) [A]48.4
Continuous Current (NO) [A]40
Intermittent Current (NO) [A]44

Technical data

Motor power22 kW / 30 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP21 / Type 1 Backplate
Frame sizeB2
RFI filterClass A2 (EMC C3)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current44 A
Continuous current (high line)40 A
Intermittent output current48.4 A
Apparent power30.5 kVA
Power loss525 W
Power, normal overload22 kW
Height664 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight29.04 kg
Gross weight32.6 kg
EAN5715253197814
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132X4810 are available on request. Ask for documents →

Other 22 kW / 30 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.