Danfoss VLT HVAC Drive FC 102 FC-102N400T4E00H2TGRAXXSXXXXAXBXCXXXXDX
132X8457

Danfoss 132X8457 - VLT HVAC Drive FC 102 (400 kW / 550 HP, IP00, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N400) 400 KW / 550 HP,
  • Three phase, 380 - 480 VAC,(E00) IP00 / Chassis
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB 3C3 + Ruggedised, Fuse + Loadsharing
  • Latest release std. SW.
  • Frame: E3H
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-102N400T4E00H2TGRAXXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN400(N400) 400 KW / 550 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE00(E00) IP00 / Chassis
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBRCoated PCB 3C3 + Ruggedised
Mains OptionAFuse + Loadsharing
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeE3H
Power 110% (NO) [KW]400
Height [mm]1578,0
Width w/ no C options [mm]507,0
Depth [mm]482,0
Depth with Option A/B [mm]482,0
kVA516
Power Loss NO [W]8036
Power Loss NO [W]6933
Continuous Current (NO) [A]745
Intermittent Current (NO) [A]820
Continuous Current (NO) [A]678
Intermittent Current (NO) [A]746

Technical data

Motor power400 kW / 550 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP00 / Chassis
Frame sizeE3H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB 3C3 + Ruggedised
Mains optionFuse + Loadsharing
FieldbusNone
Product typeFrequency converter
Continuous output current745 A
Continuous current (high line)678 A
Intermittent output current820 A
Apparent power516 kVA
Power loss8036 W
Power, normal overload400 kW
Height1578 mm
Width507 mm
Depth482 mm
Depth with A/B options482 mm
Net weight272 kg
Gross weight272.3 kg
EAN5715253235165
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132X8457 are available on request. Ask for documents →

Other 400 kW / 550 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery