Danfoss VLT AQUA Drive FC 202 FC-202N355T4E54H2XGC7XXSXXXXAXBXCXXXXD0
132X9291

Danfoss 132X9291 - VLT AQUA Drive FC 202 (355 kW / 500 HP, IP54, 380-480V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (N355) 355 KW / 500 HP,
  • Three phase, 380 - 480 VAC,(E54) IP54 / Type 12
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Latest release std. SW.
  • Frame: E1H
  • No A Option, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-202N355T4E54H2XGC7XXSXXXXAXBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingN355(N355) 355 KW / 500 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeE1H
Power 150% (HO) [KW]315
Power 110% (NO) [KW]355
Height [mm]2000,0
Width w/ no C options [mm]600,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
kVA456
Power Loss NO [W]6928
Power Loss NO [W]5910
Power Loss HO [W]6178
Power Loss HO [W]5322
Continuous Current (NO) [A]658
Intermittent Current (NO) [A]724
Continuous Current (NO) [A]590
Intermittent Current (NO) [A]649
Continuous Current (HO) [A]600
Intermittent Current (HO) [A]900
Continuous Current (HO) [A]540
Intermittent Current (HO) [A]810

Technical data

Motor power355 kW / 500 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeE1H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current658 A
Continuous current (high line)590 A
Intermittent output current724 A
Continuous current (high overload)600 A
Apparent power456 kVA
Power loss6928 W
Power, normal overload355 kW
Power, high overload315 kW
Height2000 mm
Width600 mm
Depth510 mm
Depth with A/B options510 mm
Net weight295 kg
Gross weight295.3 kg
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 132X9291 are available on request. Ask for documents →