Danfoss VLT AutomationDrive FC 302 FC-302P5K5T6E20HXXGCXXXSXXXXALBXCXXXXD0
134F0567

Danfoss 134F0567 - VLT AutomationDrive FC 302 (5.5 kW / 7.5 HP, IP20, 525-600V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P5K5) 5.5 KW / 7.5 HP,
  • Three phase, 525 - 600 VAC,(E20) IP20 / Chassis
  • No RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: A3
  • PROFINET MCA 120, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-302P5K5T6E20HXXGCXXXSXXXXALBXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP5K5(P5K5) 5.5 KW / 7.5 HP
PhaseTThree phase
Mains Voltage6525 - 600 VAC
EnclosureE20(E20) IP20 / Chassis
RFI FilterHXNo RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeA3
Power 160% (HO) [KW]5.5
Height [mm]268,0
Width w/ no C options [mm]130,0
Width w/ two C options [mm]190,0
Depth [mm]205,0
Depth with Option A/B [mm]220,0
kVA8.96
Power Loss HO [W]195
Continuous Current (HO) [A]9.5
Intermittent Current (HO) [A]15.2
Continuous Current (HO) [A]9
Intermittent Current (HO) [A]14.4

Technical data

Motor power5.5 kW / 7.5 HP
Mains voltage525 - 600 VAC
PhaseThree-phase
Protection ratingIP20 / Chassis
Frame sizeA3
RFI filterNone
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current9.5 A
Intermittent output current15.2 A
Apparent power8.96 kVA
Power loss195 W
Power, high overload5.5 kW
Height268 mm
Width130 mm
Width with C options190 mm
Depth205 mm
Depth with A/B options220 mm
Net weight6.29 kg
Gross weight7.296 kg
Packed volume27.2 L
EAN5710107402748
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134F0567 are available on request. Ask for documents →

Other 5.5 kW / 7.5 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.