Danfoss VLT HVAC Drive FC 102 FC-102P30KT4P55H1BGX1XXSXXXXAXBPCXXXXD0
134F0775

Danfoss 134F0775 - VLT HVAC Drive FC 102 (30 kW / 40 HP, IP55, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P30K) 30 KW / 40 HP,
  • Three phase, 380 - 480 VAC,IP55 / Type12 Backplate
  • (H1) RFI Class A1/B (C1)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: B2
  • No A Option, MCB-105 Relay Card
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102P30KT4P55H1BGX1XXSXXXXAXBPCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP30K(P30K) 30 KW / 40 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH1(H1) RFI Class A1/B (C1)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBPMCB-105 Relay Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeB2
Power 110% (NO) [KW]30
Height [mm]664,0
Width w/ no C options [mm]243,0
Depth [mm]261,0
Depth with Option A/B [mm]261,0
kVA42.3
Power Loss NO [W]698
Continuous Current (NO) [A]61
Intermittent Current (NO) [A]67.1
Continuous Current (NO) [A]52
Intermittent Current (NO) [A]57.2

Technical data

Motor power30 kW / 40 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeB2
RFI filterClass A1/B (EMC C1)
Brake chopperYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionMains Disconnect
FieldbusNone
Product typeFrequency converter
Continuous output current61 A
Continuous current (high line)52 A
Intermittent output current67.1 A
Apparent power42.3 kVA
Power loss698 W
Power, normal overload30 kW
Height664 mm
Width243 mm
Depth261 mm
Depth with A/B options261 mm
Net weight30.83 kg
Gross weight34.39 kg
Packed volume144.7 L
EAN5710107404803
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134F0775 are available on request. Ask for documents →

Other 30 kW / 40 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.