Danfoss VLT AutomationDrive FC 302 FC-302P1M2T7E54H2CGC3NKSXXXXAXB4CXRXXDX
134F0827

Danfoss 134F0827 - VLT AutomationDrive FC 302 (1200 kW / 1600 HP, IP54, 525-690V)

  • Frequency converter
  • NB: F-frame platform available until December 31, 2025
  • VLT® AutomationDrive FC-302
  • (P1M2) 1.2 MW / 1600 HP,
  • Three phase, 525 - 690 VAC *,(E54) IP54 / Type 12
  • RFI Filter
  • Safe Stop + Pilz Relay
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: F4
  • No A Option, MCB-114 VLT Sensor Input
  • MCB-113 Ext. Relay Card, No D option
Model code:
FC-302P1M2T7E54H2CGC3NKSXXXXAXB4CXRXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP1M2(P1M2) 1.2 MW / 1600 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopCSafe Stop + Pilz Relay
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation ANTwo 10-16A man motor star
Adaptation BKF Frame Common Motor Term
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionB4MCB-114 VLT Sensor Input
C0 Option MCOCXNo C0 option
C1 OptionRMCB-113 Ext. Relay Card
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeF4
Power 150% (HO) [KW]1200
Power 110% (NO) [KW]1400
Height [mm]2204,0
Width w/ no C options [mm]2400,0
Depth [mm]606,0
Depth with Option A/B [mm]606,0
kVA1506
Power Loss NO [W]18536
Power Loss NO [W]19247
Power Loss HO [W]16089
Power Loss HO [W]16719
Continuous Current (NO) [A]1479
Intermittent Current (NO) [A]1627
Continuous Current (NO) [A]1415
Intermittent Current (NO) [A]1557
Continuous Current (HO) [A]1317
Intermittent Current (HO) [A]1976
Continuous Current (HO) [A]1260
Intermittent Current (HO) [A]1890

Technical data

Motor power1200 kW / 1600 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeF4
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current1479 A
Continuous current (high line)1415 A
Intermittent output current1627 A
Continuous current (high overload)1317 A
Apparent power1506 kVA
Power loss18536 W
Power, normal overload1400 kW
Power, high overload1200 kW
Height2204 mm
Width2400 mm
Depth606 mm
Depth with A/B options606 mm
Net weight1246 kg
Gross weight1246.3 kg
EAN5710107405268
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134F0827 are available on request. Ask for documents →