Danfoss VLT AQUA Drive FC 202 FC-202N315T4E21H2XGC7XXSXXXXAXBXCXXXXDX
134F9719

Danfoss 134F9719 - VLT AQUA Drive FC 202 (315 kW / 450 HP, IP21, 380-480V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (N315) 315 KW / 450 HP,
  • Three phase, 380 - 480 VAC,IP21 / Type 1
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Latest release std. SW.
  • Frame: D2H
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-202N315T4E21H2XGC7XXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingN315(N315) 315 KW / 450 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE21IP21 / Type 1
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD2H
Power 150% (HO) [KW]250
Power 110% (NO) [KW]315
Height [mm]1060,0
Width w/ no C options [mm]420,0
Depth [mm]378,0
Depth with Option A/B [mm]378,0
kVA407
Power Loss NO [W]6674
Power Loss NO [W]5714
Power Loss HO [W]5004
Power Loss HO [W]4458
Continuous Current (NO) [A]588
Intermittent Current (NO) [A]647
Continuous Current (NO) [A]535
Intermittent Current (NO) [A]588
Continuous Current (HO) [A]480
Intermittent Current (HO) [A]720
Continuous Current (HO) [A]443
Intermittent Current (HO) [A]664

Technical data

Motor power315 kW / 450 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeD2H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current588 A
Continuous current (high line)535 A
Intermittent output current647 A
Continuous current (high overload)480 A
Apparent power407 kVA
Power loss6674 W
Power, normal overload315 kW
Power, high overload250 kW
Height1060 mm
Width420 mm
Depth378 mm
Depth with A/B options378 mm
Net weight132 kg
Gross weight147 kg
EAN5710107500116
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134F9719 are available on request. Ask for documents →

Other 315 kW / 450 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.