Danfoss VLT AutomationDrive FC 302 FC-302P1M0T7E21H2MGCEEXSXXXXA0B4CXRXXD0
134G3045

Danfoss 134G3045 - VLT AutomationDrive FC 302 (1000 kW / 1350 HP, IP21, 525-690V)

  • Frequency converter
  • NB: F-frame platform available until December 31, 2025
  • VLT® AutomationDrive FC-302
  • (P1M0) 1.0 MW / 1350 HP, Specific Ratings: 850kW@525-550V, 1150HP@575V, 1000kW@690V
  • Three phase, 525 - 690 VAC *,IP21 / Type 1
  • RFI Filter
  • E stop (incl Relé Pliz)
  • Graphical Loc. Cont. Panel
  • Coated PCB, Disconnect+Contactor+Fuse
  • Latest release std. SW.
  • Frame: F4
  • PROFIBUS DP MCA 101, MCB-114 VLT Sensor Input
  • MCB-113 Ext. Relay Card, MCB-107 24V DC backup
Model code:
FC-302P1M0T7E21H2MGCEEXSXXXXA0B4CXRXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP1M0(P1M0) 1.0 MW / 1350 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE21IP21 / Type 1
RFI FilterH2RFI Filter
Brake - Safe StopME stop (incl Relé Pliz)
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionEDisconnect+Contactor+Fuse
Adaptation AE30A fuse prot power termin
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionB4MCB-114 VLT Sensor Input
C0 Option MCOCXNo C0 option
C1 OptionRMCB-113 Ext. Relay Card
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeF4
Power 150% (HO) [KW]1000
Power 110% (NO) [KW]1200
Height [mm]2204,0
Width w/ no C options [mm]2400,0
Depth [mm]606,0
Depth with Option A/B [mm]606,0
kVA1267
Power Loss NO [W]16190
Power Loss NO [W]16801
Power Loss HO [W]13269
Power Loss HO [W]13801
Continuous Current (NO) [A]1317
Intermittent Current (NO) [A]1449
Continuous Current (NO) [A]1260
Intermittent Current (NO) [A]1386
Continuous Current (HO) [A]1108
Intermittent Current (HO) [A]1662
Continuous Current (HO) [A]1060
Intermittent Current (HO) [A]1590
Power Rating at 525-550V850kW
Power Rating at 575V1150HP
Power Rating at 690V1000kW

Technical data

Motor power1000 kW / 1350 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeF4
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Contactor + Fuse
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current1317 A
Continuous current (high line)1260 A
Intermittent output current1449 A
Continuous current (high overload)1108 A
Apparent power1267 kVA
Power loss16190 W
Power, normal overload1200 kW
Power, high overload1000 kW
Height2204 mm
Width2400 mm
Depth606 mm
Depth with A/B options606 mm
Net weight1246 kg
Gross weight1246.3 kg
EAN5710107533459
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134G3045 are available on request. Ask for documents →