Danfoss VLT AutomationDrive FC 302 FC-302P45KT7E21H2XGCDXXSXXXXA0BKCXXXXD0
134G9696

Danfoss 134G9696 - VLT AutomationDrive FC 302 (45 kW / 60 HP, IP21, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P45K) 45 KW / 60 HP, Specific Ratings: 37kW@525-550V, 50HP@575V, 45kW@690V
  • Three phase, 525 - 690 VAC *,IP21 / Type 1
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Loadsharing
  • Latest release std. SW.
  • Frame: C2
  • PROFIBUS DP MCA 101, MCB-101 General purp. I/O
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-302P45KT7E21H2XGCDXXSXXXXA0BKCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP45K(P45K) 45 KW / 60 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE21IP21 / Type 1
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionDLoadsharing
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBKMCB-101 General purp. I/O
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeC2
Power 150% (HO) [KW]45
Power 110% (NO) [KW]55
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA62.1
Power Loss NO [W]1100
Power Loss HO [W]900
Continuous Current (NO) [A]65
Intermittent Current (NO) [A]71.5
Continuous Current (NO) [A]62
Intermittent Current (NO) [A]68.2
Continuous Current (HO) [A]54
Intermittent Current (HO) [A]81
Continuous Current (HO) [A]52
Intermittent Current (HO) [A]78
Power Rating at 525-550V37kW
Power Rating at 575V50HP
Power Rating at 690V45kW

Technical data

Motor power45 kW / 60 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeC2
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionLoadsharing
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current65 A
Continuous current (high line)62 A
Intermittent output current71.5 A
Continuous current (high overload)54 A
Apparent power62.1 kVA
Power loss1100 W
Power, normal overload55 kW
Power, high overload45 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight54.01 kg
Gross weight57.35 kg
Packed volume232.7 L
EAN5710107646715
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134G9696 are available on request. Ask for documents →

Other 45 kW / 60 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.