Danfoss VLT HVAC Drive FC 102 FC-102P630T4E54H2XGCXXKSXXXXA4BXCXXXXDX
134H8087

Danfoss 134H8087 - VLT HVAC Drive FC 102 (630 kW / 900 HP, IP54, 380-480V)

  • Frequency Converter
  • NB: F-frame platform available until December 31, 2025
  • VLT® HVAC Drive FC-102
  • (P630) 630 KW / 900 HP,
  • Three phase, 380 - 480 VAC,(E54) IP54 / Type 12
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: F1
  • DeviceNet MCA 104, No B Option
  • No C1 option, No D option
Model code:
FC-102P630T4E54H2XGCXXKSXXXXA4BXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP630(P630) 630 KW / 900 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BKF Frame Common Motor Term
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA4DeviceNet MCA 104
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeF1
Power 110% (NO) [KW]630
Height [mm]2204,0
Width w/ no C options [mm]1400,0
Depth [mm]606,0
Depth with Option A/B [mm]606,0
kVA776
Power Loss NO [W]12512
Power Loss NO [W]11595
Continuous Current (NO) [A]1120
Intermittent Current (NO) [A]1232
Continuous Current (NO) [A]1050
Intermittent Current (NO) [A]1155

Technical data

Motor power630 kW / 900 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeF1
RFI filterClass A2 (EMC C3)
Brake chopperNo
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
FieldbusDeviceNet MCA 104
Product typeFrequency converter
Continuous output current1120 A
Continuous current (high line)1050 A
Intermittent output current1232 A
Apparent power776 kVA
Power loss12512 W
Power, normal overload630 kW
Height2204 mm
Width1400 mm
Depth606 mm
Depth with A/B options606 mm
Net weight1899 kg
Gross weight1899.3 kg
EAN5710107732135
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134H8087 are available on request. Ask for documents →

Other 630 kW / 900 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery