Danfoss VLT HVAC Drive FC 102 FC-102N160T4E21H4TGC7XXSXXXXA0BXCXXXXD0
134L1679

Danfoss 134L1679 - VLT HVAC Drive FC 102 (160 kW / 250 HP, IP21, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N160) 160 KW / 250 HP,
  • Three phase, 380 - 480 VAC,IP21 / Type 1
  • RFI class A1 (C2)
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Latest release std. SW.
  • Frame: D1H
  • PROFIBUS DP MCA 101, No B Option
  • No C1 option, MCB-107 24V DC backup
Model code:
FC-102N160T4E21H4TGC7XXSXXXXA0BXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN160(N160) 160 KW / 250 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE21IP21 / Type 1
RFI FilterH4RFI class A1 (C2)
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeD1H
Power 110% (NO) [KW]160
Height [mm]901,0
Width w/ no C options [mm]325,0
Depth [mm]378,0
Depth with Option A/B [mm]378,0
kVA218
Power Loss NO [W]3764
Power Loss NO [W]3628
Continuous Current (NO) [A]315
Intermittent Current (NO) [A]346
Continuous Current (NO) [A]302
Intermittent Current (NO) [A]332

Technical data

Motor power160 kW / 250 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP21 / Type 1
Frame sizeD1H
RFI filterClass A1 (EMC C2)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current315 A
Continuous current (high line)302 A
Intermittent output current346 A
Apparent power218 kVA
Power loss3764 W
Power, normal overload160 kW
Height901 mm
Width325 mm
Depth378 mm
Depth with A/B options378 mm
Net weight129 kg
Gross weight129.3 kg
EAN5710107768349
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134L1679 are available on request. Ask for documents →

Other 160 kW / 250 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.