Danfoss VLT AutomationDrive FC 302 FC-302P710T7C21H2MGCEXKSXXXXAXBXCXXXXDX
134L6342

Danfoss 134L6342 - VLT AutomationDrive FC 302 (710 kW / 1000 HP, IP21, 525-690V)

  • Frequency converter
  • NB: F-frame platform available until December 31, 2025
  • VLT® AutomationDrive FC-302
  • (P710) 710 KW / 1000 HP, Specific Ratings: 560kW@525-550V, 750HP@575V, 710kW@690V
  • Three phase, 525 - 690 VAC *,SS BackChnl IP21/Type 1
  • RFI Filter
  • E stop (incl Relé Pliz)
  • Graphical Loc. Cont. Panel
  • Coated PCB, Disconnect+Contactor+Fuse
  • Latest release std. SW.
  • Frame: F3
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-302P710T7C21H2MGCEXKSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP710(P710) 710 KW / 1000 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureC21SS BackChnl IP21/Type 1
RFI FilterH2RFI Filter
Brake - Safe StopME stop (incl Relé Pliz)
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionEDisconnect+Contactor+Fuse
Adaptation AXStandard Cable Entries
Adaptation BKF Frame Common Motor Term
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeF3
Power 150% (HO) [KW]710
Power 110% (NO) [KW]800
Height [mm]2204,0
Width w/ no C options [mm]2000,0
Depth [mm]606,0
Depth with Option A/B [mm]606,0
kVA872
Power Loss NO [W]10872
Power Loss NO [W]11304
Power Loss HO [W]9165
Power Loss HO [W]9537
Continuous Current (NO) [A]889
Intermittent Current (NO) [A]978
Continuous Current (NO) [A]850
Intermittent Current (NO) [A]935
Continuous Current (HO) [A]763
Intermittent Current (HO) [A]1144
Continuous Current (HO) [A]730
Intermittent Current (HO) [A]1095
Power Rating at 525-550V560kW
Power Rating at 575V750HP
Power Rating at 690V710kW

Technical data

Motor power710 kW / 1000 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingSS BackChnl IP21/Type 1
Frame sizeF3
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Contactor + Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current889 A
Continuous current (high line)850 A
Intermittent output current978 A
Continuous current (high overload)763 A
Apparent power872 kVA
Power loss10872 W
Power, normal overload800 kW
Power, high overload710 kW
Height2204 mm
Width2000 mm
Depth606 mm
Depth with A/B options606 mm
Net weight1004 kg
Gross weight1004.3 kg
EAN5710107815371
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134L6342 are available on request. Ask for documents →

Other 710 kW / 1000 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery