Danfoss VLT AutomationDrive FC 302 FC-302P315T5E2MN4XGC7XXSXXXXA0BXCXXXXDX
134N0332

Danfoss 134N0332 - VLT AutomationDrive FC 302 (315 kW / 450 HP, IP21, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P315) 315 KW / 450 HP, Three phase
  • 380 - 500 VAC, IP21/Type 1+mains shield
  • LHD - AAF006 filter + A1 RFI
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Latest release std. SW.
  • Frame: E9
  • No C1 option, No D option
  • PROFIBUS DP MCA 101, No B Option
Model code:
FC-302P315T5E2MN4XGC7XXSXXXXA0BXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP315(P315) 315 KW / 450 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE2MIP21/Type 1+mains shield
RFI FilterN4LHD - AAF006 filter + A1 RFI
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeE9
Power 150% (HO) [KW]315
Power 110% (NO) [KW]355
Height [mm]2000,0
Width w/ no C options [mm]1200,0
Depth [mm]500,0
Depth with Option A/B [mm]500,0
kVA416
Power Loss NO [W]15320
Power Loss NO [W]14083
Continuous Current (NO) [A]658
Intermittent Current (NO) [A]724
Continuous Current (NO) [A]590
Intermittent Current (NO) [A]649
Continuous Current (HO) [A]600
Intermittent Current (HO) [A]900
Continuous Current (HO) [A]540
Intermittent Current (HO) [A]810

Technical data

Motor power315 kW / 450 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP21/Type 1+mains shield
Frame sizeE9
RFI filterClass A1 (EMC C2)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current658 A
Continuous current (high line)590 A
Intermittent output current724 A
Continuous current (high overload)600 A
Apparent power416 kVA
Power loss15320 W
Power, normal overload355 kW
Power, high overload315 kW
Height2000 mm
Width1200 mm
Depth500 mm
Depth with A/B options500 mm
Net weight270 kg
Gross weight270.3 kg
Packed volume0 L
EAN5710107855605
ECCN (EU)X.A.I.003
ECCN (US)3A999

Documents

Operating guides, design guides, certificates and CAD drawings for 134N0332 are available on request. Ask for documents →

Other 315 kW / 450 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery