Danfoss VLT HVAC Drive FC 102 FC-102N160T4E5MH2XLC3XXSXXXXA0BXCXXXXDX
134U4057

Danfoss 134U4057 - VLT HVAC Drive FC 102 (160 kW / 250 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N160) 160 KW / 250 HP,
  • Three phase, 380 - 480 VAC,IP54/Type 12+main shield
  • RFI Filter
  • No brake chopper
  • Graphical LCP + USB
  • Coated PCB, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: D5H
  • PROFIBUS DP MCA 101, No B Option
  • No C1 option, No D option
Model code:
FC-102N160T4E5MH2XLC3XXSXXXXA0BXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN160(N160) 160 KW / 250 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE5MIP54/Type 12+main shield
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPLGraphical LCP + USB
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD5H
Power 110% (NO) [KW]160
Height [mm]1324,0
Width w/ no C options [mm]325,0
Depth [mm]381,0
Depth with Option A/B [mm]381,0
kVA218
Power Loss NO [W]3764
Power Loss NO [W]3628
Continuous Current (NO) [A]315
Intermittent Current (NO) [A]346
Continuous Current (NO) [A]302
Intermittent Current (NO) [A]332

Technical data

Motor power160 kW / 250 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54/Type 12+main shield
Frame sizeD5H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Control panelGraphical LCP + USB
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current315 A
Continuous current (high line)302 A
Intermittent output current346 A
Apparent power218 kVA
Power loss3764 W
Power, normal overload160 kW
Height1324 mm
Width325 mm
Depth381 mm
Depth with A/B options381 mm
Net weight101 kg
Gross weight141 kg
EAN5710108000141
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134U4057 are available on request. Ask for documents →

Other 160 kW / 250 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.