Danfoss VLT HVAC Drive FC 102 FC-102N200T7E54H2TGR3XXSXXXXAXBXCXXXXDX
134U4352

Danfoss 134U4352 - VLT HVAC Drive FC 102 (200 kW / 300 HP, IP54, 525-690V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N200) 200 KW / 300 HP, Specific Ratings: 160kW@525-550V, 250HP@575V, 200kW@690V
  • Three phase, 525 - 690 VAC *,(E54) IP54 / Type 12
  • RFI Filter
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB 3C3 + Ruggedised, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: D7H
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-102N200T7E54H2TGR3XXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN200(N200) 200 KW / 300 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBRCoated PCB 3C3 + Ruggedised
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD7H
Power 110% (NO) [KW]200
Height [mm]1978,0
Width w/ no C options [mm]420,0
Depth [mm]386,0
Depth with Option A/B [mm]386,0
kVA289
Power Loss NO [W]3071
Power Loss NO [W]3172
Continuous Current (NO) [A]253
Intermittent Current (NO) [A]278
Continuous Current (NO) [A]242
Intermittent Current (NO) [A]266
Power Rating at 525-550V160kW
Power Rating at 575V250HP
Power Rating at 690V200kW

Technical data

Motor power200 kW / 300 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeD7H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB 3C3 + Ruggedised
Mains optionMains Disconnect + Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current253 A
Continuous current (high line)242 A
Intermittent output current278 A
Apparent power289 kVA
Power loss3071 W
Power, normal overload200 kW
Height1978 mm
Width420 mm
Depth386 mm
Depth with A/B options386 mm
Net weight200 kg
Gross weight200.3 kg
EAN5710108003371
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134U4352 are available on request. Ask for documents →

Other 200 kW / 300 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.