Danfoss VLT Refrigeration Drive FC 103 FC-103N250T4E54H2TGC7XXSXXXXAXBXCXXXXDX
134U7490

Danfoss 134U7490 - VLT Refrigeration Drive FC 103 (250 kW / 350 HP, IP54, 380-480V)

  • Frequency converter
  • VLT® Refrigeration Drive FC-103
  • (N250) 250 KW / 350 HP,
  • Three phase, 380 - 480 VAC,(E54) IP54 / Type 12
  • RFI filter Class A2
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Latest release std. SW.
  • No A Option, No B Option
  • No C1 option, No D option
  • Frame: D2H
Model code:
FC-103N250T4E54H2TGC7XXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® Refrigeration Drive
Series103
Power RatingN250(N250) 250 KW / 350 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI filter Class A2
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD2H
Power 110% (NO) [KW]250
Height [mm]1060,0
Width w/ no C options [mm]420,0
Depth [mm]378,0
Depth with Option A/B [mm]378,0
kVA333
Power Loss NO [W]5129
Power Loss NO [W]4558
Continuous Current (NO) [A]480
Intermittent Current (NO) [A]528
Continuous Current (NO) [A]443
Intermittent Current (NO) [A]487

Technical data

Motor power250 kW / 350 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeD2H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current480 A
Continuous current (high line)443 A
Intermittent output current528 A
Apparent power333 kVA
Power loss5129 W
Power, normal overload250 kW
Height1060 mm
Width420 mm
Depth378 mm
Depth with A/B options378 mm
Net weight125 kg
Gross weight125.3 kg
EAN5710108035358
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 134U7490 are available on request. Ask for documents →

Other 250 kW / 350 HP variants in VLT Refrigeration Drive FC 103

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.