Danfoss VLT HVAC Drive FC 102 FC-102N250T4E54N4TGCXXXSXXXXA0BXCXXXXD0
135N9927

Danfoss 135N9927 - VLT HVAC Drive FC 102 (250 kW / 350 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (N250) 250 KW / 350 HP, Three phase
  • 380 - 480 VAC, (E54) IP54 / Type 12
  • LHD - AAF006 filter + A1 RFI
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: D2n
  • No C1 option, MCB-107 24V DC backup
  • PROFIBUS DP MCA 101, No B Option
Model code:
FC-102N250T4E54N4TGCXXXSXXXXA0BXCXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN250(N250) 250 KW / 350 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterN4LHD - AAF006 filter + A1 RFI
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionA0PROFIBUS DP MCA 101
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeD2ND2n
Power 110% (NO) [KW]250
Height [mm]1780,0
Width w/ no C options [mm]1020,0
Depth [mm]380,0
Depth with Option A/B [mm]380,0
kVA333
Power Loss NO [W]5129
Power Loss NO [W]4558
Continuous Current (NO) [A]480
Intermittent Current (NO) [A]528
Continuous Current (NO) [A]443
Intermittent Current (NO) [A]487

Technical data

Motor power250 kW / 350 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeD2n
RFI filterClass A1 (EMC C2)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
FieldbusPROFIBUS DP MCA 101
Product typeFrequency converter
Continuous output current480 A
Continuous current (high line)443 A
Intermittent output current528 A
Apparent power333 kVA
Power loss5129 W
Power, normal overload250 kW
Height1780 mm
Width1020 mm
Depth380 mm
Depth with A/B options380 mm
Net weight117 kg
Gross weight132 kg
Packed volume0 L
EAN5710108261474
ECCN (US)3A999

Documents

Operating guides, design guides, certificates and CAD drawings for 135N9927 are available on request. Ask for documents →

Other 250 kW / 350 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.