Danfoss VLT AutomationDrive FC 302 FC-302P55KT5P55H5BGC1XXSXXXXAXBXCXXXXDX
135U7733

Danfoss 135U7733 - VLT AutomationDrive FC 302 (55 kW / 75 HP, IP55, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P55K) 55 KW / 75 HP,
  • Three phase, 380 - 500 VAC,IP55 / Type12 Backplate
  • Marine,ruggedis RFI A2(C3)
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Latest release std. SW.
  • Frame: C2
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-302P55KT5P55H5BGC1XXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP55K(P55K) 55 KW / 75 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureP55IP55 / Type12 Backplate
RFI FilterH5Marine,ruggedis RFI A2(C3)
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 150% (HO) [KW]55
Power 110% (NO) [KW]75
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA73.4
Power Loss NO [W]1384
Power Loss HO [W]1022
Continuous Current (NO) [A]147
Intermittent Current (NO) [A]162
Continuous Current (NO) [A]130
Intermittent Current (NO) [A]143
Continuous Current (HO) [A]106
Intermittent Current (HO) [A]159
Continuous Current (HO) [A]105
Intermittent Current (HO) [A]158

Technical data

Motor power55 kW / 75 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP55 / Type12 Backplate
Frame sizeC2
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
FieldbusNone
Product typeFrequency converter
Continuous output current147 A
Continuous current (high line)130 A
Intermittent output current162 A
Continuous current (high overload)106 A
Apparent power73.4 kVA
Power loss1384 W
Power, normal overload75 kW
Power, high overload55 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight57 kg
Gross weight58.84 kg
EAN5710108339968
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 135U7733 are available on request. Ask for documents →

Other 55 kW / 75 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.