Danfoss VLT AutomationDrive FC 302 FC-302N250T7E54H2BGR3XXSXXXXAXBKCXXXXDX
135X5457

Danfoss 135X5457 - VLT AutomationDrive FC 302 (250 kW / 350 HP, IP54, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (N250) 250 KW / 350 HP, Specific Ratings: 200kW@525-550V, 300HP@575V, 250kW@690V
  • Three phase, 525 - 690 VAC *,(E54) IP54 / Type 12
  • RFI Filter
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB 3C3 + Ruggedised, Mains Disconnect + Fuse
  • Latest release std. SW.
  • Frame: D7H
  • No A Option, MCB-101 General purp. I/O
  • No C1 option, No D option
Model code:
FC-302N250T7E54H2BGR3XXSXXXXAXBKCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingN250(N250) 250 KW / 350 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE54(E54) IP54 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBRCoated PCB 3C3 + Ruggedised
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBKMCB-101 General purp. I/O
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeD7H
Power 150% (HO) [KW]250
Power 110% (NO) [KW]315
Height [mm]1978,0
Width w/ no C options [mm]420,0
Depth [mm]386,0
Depth with Option A/B [mm]386,0
kVA347
Power Loss NO [W]4465
Power Loss NO [W]4614
Power Loss HO [W]3642
Power Loss HO [W]3771
Continuous Current (NO) [A]360
Intermittent Current (NO) [A]396
Continuous Current (NO) [A]344
Intermittent Current (NO) [A]378
Continuous Current (HO) [A]303
Intermittent Current (HO) [A]454
Continuous Current (HO) [A]290
Intermittent Current (HO) [A]435
Power Rating at 525-550V200kW
Power Rating at 575V300HP
Power Rating at 690V250kW

Technical data

Motor power250 kW / 350 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeD7H
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB 3C3 + Ruggedised
Mains optionMains Disconnect + Fuse
FieldbusNone
Product typeFrequency converter
Continuous output current360 A
Continuous current (high line)344 A
Intermittent output current396 A
Continuous current (high overload)303 A
Apparent power347 kVA
Power loss4465 W
Power, normal overload315 kW
Power, high overload250 kW
Height1978 mm
Width420 mm
Depth386 mm
Depth with A/B options386 mm
Net weight200 kg
Gross weight200.3 kg
EAN5710108417611
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 135X5457 are available on request. Ask for documents →

Other 250 kW / 350 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.