136G4354
Danfoss 136G4354 - VLT HVAC Drive FC 102 (500 kW / 650 HP, IP21, 380-480V)
- Frequency Converter
- VLT® HVAC Drive FC-102
- (P500) 500 KW / 650 HP, Three phase
- 380 - 480 VAC, IP21 / Type 1
- LHD - AAF006 filter + A2 RFI
- Brake chopper + Safe stop
- Graphical Loc. Cont. Panel
- Coated PCB, Mains Disconnect + Fuse
- Latest release std. SW.
- Frame: F18
- No C1 option, No D option
- No A Option, MCB-112 PTC Therm. Card
Model code:
FC-102P500T4E21N2UGC3XXSXXXXAXB2CXXXXDX
FC-102P500T4E21N2UGC3XXSXXXXAXB2CXXXXDX
Similar products
- Genuine Danfoss products
- Danfoss manufacturer warranty
- Reply within one business day
Product details
| Product Group | FC- | VLT® HVAC Drive FC- |
| Series | 102 | |
| Power Rating | P500 | (P500) 500 KW / 650 HP |
| Phase | T | Three phase |
| Mains Voltage | 4 | 380 - 480 VAC |
| Enclosure | E21 | IP21 / Type 1 |
| RFI Filter | N2 | LHD - AAF006 filter + A2 RFI |
| Brake - Safe Stop | U | Brake chopper + Safe stop |
| LCP | G | Graphical Loc. Cont. Panel |
| Coating PCB | C | Coated PCB |
| Mains Option | 3 | Mains Disconnect + Fuse |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| A Option | AX | No A Option |
| B Option | B2 | MCB-112 PTC Therm. Card |
| C0 Option MCO | CX | No C0 option |
| C1 Option | X | No C1 option |
| C Option Software | XX | No software option |
| D Option | DX | No D option |
| Frame Size | F18 | |
| Power 110% (NO) [KW] | 500 | |
| Height [mm] | 2277,0 | |
| Width w/ no C options [mm] | 2802,0 | |
| Depth [mm] | 607,0 | |
| Depth with Option A/B [mm] | 607,0 | |
| kVA | 610 | |
| Power Loss NO [W] | 10162 | |
| Power Loss NO [W] | 8876 | |
| Continuous Current (NO) [A] | 880 | |
| Intermittent Current (NO) [A] | 968 | |
| Continuous Current (NO) [A] | 780 | |
| Intermittent Current (NO) [A] | 858 |
Technical data
| Motor power | 500 kW / 650 HP | |
| Mains voltage | 380 - 480 VAC | |
| Phase | Three-phase | |
| Protection rating | IP21 / Type 1 | |
| Frame size | F18 | |
| RFI filter | Class A2 (EMC C3) | |
| Brake chopper | Yes | |
| Safe Torque Off | Yes | |
| Control panel | Graphical LCP | |
| PCB coating | Coated PCB | |
| Mains option | Mains Disconnect + Fuse | |
| Fieldbus | None | |
| Product type | Frequency converter | |
| Continuous output current | 880 A | |
| Continuous current (high line) | 780 A | |
| Intermittent output current | 968 A | |
| Apparent power | 610 kVA | |
| Power loss | 10162 W | |
| Power, normal overload | 500 kW | |
| Height | 2277 mm | |
| Width | 2802 mm | |
| Depth | 607 mm | |
| Depth with A/B options | 607 mm | |
| Net weight | 1899 kg | |
| Gross weight | 1899.3 kg | |
| Packed volume | 0 L | |
| EAN | 5710108608064 | |
| ECCN (US) | 3A999 | |
Documents
Operating guides, design guides, certificates and CAD drawings for 136G4354 are available on request. Ask for documents →
Other 500 kW / 650 HP variants in VLT HVAC Drive FC 102
- 137G4601 IP00 · Class A2 · E4H
- 136N2076 IP00 · Class A2 · E4H
- 135U3557 IP00 · Class A2 · E4H
- 136G1393 IP00 · Class A2 · E4H
- 135N9398 IP00 · Class A1 · E4H
- 137G1865 IP00 · Class A1 · E4H
- 135N6262 IP00 · Class A2 · DA2
- 134X4766 IP00 · Class A2 · DA2
- 135N4264 IP00 · Class A2 · DA2
- 134X7046 IP00 · Class A2 · DA2
- 134X3933 IP00 · Class A2 · DA2
- 135N0442 IP00 · Class A1 · DA2
- 135U0247 IP00 · Class A2 · DB2
- 134X9821 IP00 · Class A1 · DB2
- 167F3963 IP20 · Class A2 · E4H
- 137G9379 IP20 · Class A2 · E4H
- 135U2900 IP20 · Class A2 · E4H
- 136U0086 IP20 · Class A1 · E4H
- 136F8227 IP20 · Class A2 · E4H
- 136F8157 IP20 · Class A2 · E4H
- 137G2331 IP20 · Class A2 · E4H
- 137N0379 IP20 · Class A2 · E4H
- 167G4497 IP20 · Class A2 · E4H
- 136F6564 IP20 · Class A2 · E4H