Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingN500(N500) 500 KW / 650 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE2MIP21/Type 1+mains shield
RFI FilterH2RFI Filter
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option3Mains Disconnect + Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionB4MCB-114 VLT Sensor Input
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeE2H
Power 110% (NO) [KW]500
Height [mm]2000,0
Width w/ no C options [mm]700,0
Depth [mm]510,0
Depth with Option A/B [mm]510,0
kVA610
Power Loss NO [W]9473
Power Loss NO [W]7809
Continuous Current (NO) [A]880
Intermittent Current (NO) [A]968
Continuous Current (NO) [A]780
Intermittent Current (NO) [A]858

Technical data

Motor power500 kW / 650 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP21/Type 1+mains shield
Frame sizeE2H
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect + Fuse
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current880 A
Continuous current (high line)780 A
Intermittent output current968 A
Apparent power610 kVA
Power loss9473 W
Power, normal overload500 kW
Height2000 mm
Width700 mm
Depth510 mm
Depth with A/B options510 mm
Net weight318 kg
Gross weight318.3 kg
EAN5710108623951
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 136G5938 are available on request. Ask for documents →

Other 500 kW / 650 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.