Danfoss VLT AutomationDrive FC 302 FC-302P45KT7E55H2XXCXXXSXXXXAXBXCXXXXDX
136X2541

Danfoss 136X2541 - VLT AutomationDrive FC 302 (45 kW / 60 HP, IP55, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P45K) 45 KW / 60 HP, Specific Ratings: 37kW@525-550V, 50HP@575V, 45kW@690V
  • Three phase, 525 - 690 VAC *,IP55 / Type 12
  • RFI Filter
  • No brake chopper
  • No Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: C2
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-302P45KT7E55H2XXCXXXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP45K(P45K) 45 KW / 60 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureE55IP55 / Type 12
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPXNo Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 150% (HO) [KW]45
Power 110% (NO) [KW]55
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA62.1
Power Loss NO [W]1100
Power Loss HO [W]900
Continuous Current (NO) [A]65
Intermittent Current (NO) [A]71.5
Continuous Current (NO) [A]62
Intermittent Current (NO) [A]68.2
Continuous Current (HO) [A]54
Intermittent Current (HO) [A]81
Continuous Current (HO) [A]52
Intermittent Current (HO) [A]78
Power Rating at 525-550V37kW
Power Rating at 575V50HP
Power Rating at 690V45kW

Technical data

Motor power45 kW / 60 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP55 / Type 12
Frame sizeC2
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelNone
PCB coatingCoated PCB
Mains optionNone
FieldbusNone
Product typeFrequency converter
Continuous output current65 A
Continuous current (high line)62 A
Intermittent output current71.5 A
Continuous current (high overload)54 A
Apparent power62.1 kVA
Power loss1100 W
Power, normal overload55 kW
Power, high overload45 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight55.2 kg
Gross weight58.54 kg
Packed volume232.7 L
EAN5714853107162
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 136X2541 are available on request. Ask for documents →

Other 45 kW / 60 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.