Danfoss VLT AutomationDrive FC 302 FC-302P75KT5E66H2XGC1XXLX1XXAXBXCXXXXDX
136Z1867

Danfoss 136Z1867 - VLT AutomationDrive FC 302 (75 kW / 100 HP, IP66, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P75K) 75 KW / 100 HP,
  • Three phase, 380 - 500 VAC,(E66) IP66 / NEMA 4X
  • RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, Mains Disconnect
  • Condition Based Monitoring CBM
  • Frame: C2
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-302P75KT5E66H2XGC1XXLX1XXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP75K(P75K) 75 KW / 100 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE66(E66) IP66 / NEMA 4X
RFI FilterH2RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option1Mains Disconnect
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseLX1XCondition Based Monitoring CBM
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 150% (HO) [KW]75
Power 110% (NO) [KW]90
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA102
Power Loss NO [W]1474
Power Loss HO [W]1232
Continuous Current (NO) [A]177
Intermittent Current (NO) [A]195
Continuous Current (NO) [A]160
Intermittent Current (NO) [A]176
Continuous Current (HO) [A]147
Intermittent Current (HO) [A]220
Continuous Current (HO) [A]130
Intermittent Current (HO) [A]195

Technical data

Motor power75 kW / 100 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP66 / NEMA 4X
Frame sizeC2
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionMains Disconnect
FieldbusNone
Product typeFrequency converter
Continuous output current177 A
Continuous current (high line)160 A
Intermittent output current195 A
Continuous current (high overload)147 A
Apparent power102 kVA
Power loss1474 W
Power, normal overload90 kW
Power, high overload75 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight55.81 kg
Gross weight57.65 kg
EAN5714853207060
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 136Z1867 are available on request. Ask for documents →

Other 75 kW / 100 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.