137G0734
Danfoss 137G0734 - VLT HVAC Drive FC 102 (250 kW / 350 HP, IP21, 380-480V)
- Frequency Converter
- VLT® HVAC Drive FC-102
- (N250) 250 KW / 350 HP, Three phase
- 380 - 480 VAC, IP21/Type 1+mains shield
- LHD - AAF006 filter + A2 RFI
- Safe Stop
- Graphical Loc. Cont. Panel
- Coated PCB, Mains Disconnect + Fuse
- Latest release std. SW.
- Frame: D2n
- No C1 option, MCB-107 24V DC backup
- PROFINET MCA 120, MCB-114 VLT Sensor Input
Model code:
FC-102N250T4E2MN2TGC3XXSXXXXALB4CXXXXD0
FC-102N250T4E2MN2TGC3XXSXXXXALB4CXXXXD0
Similar products
- Genuine Danfoss products
- Danfoss manufacturer warranty
- Reply within one business day
Product details
| Product Group | FC- | VLT® HVAC Drive FC- |
| Series | 102 | |
| Power Rating | N250 | (N250) 250 KW / 350 HP |
| Phase | T | Three phase |
| Mains Voltage | 4 | 380 - 480 VAC |
| Enclosure | E2M | IP21/Type 1+mains shield |
| RFI Filter | N2 | LHD - AAF006 filter + A2 RFI |
| Brake - Safe Stop | T | Safe Stop |
| LCP | G | Graphical Loc. Cont. Panel |
| Coating PCB | C | Coated PCB |
| Mains Option | 3 | Mains Disconnect + Fuse |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| A Option | AL | PROFINET MCA 120 |
| B Option | B4 | MCB-114 VLT Sensor Input |
| C0 Option MCO | CX | No C0 option |
| C1 Option | X | No C1 option |
| C Option Software | XX | No software option |
| D Option | D0 | MCB-107 24V DC backup |
| Frame Size | D2N | D2n |
| Power 110% (NO) [KW] | 250 | |
| Height [mm] | 1780,0 | |
| Width w/ no C options [mm] | 1020,0 | |
| Depth [mm] | 380,0 | |
| Depth with Option A/B [mm] | 380,0 | |
| kVA | 333 | |
| Power Loss NO [W] | 11371 | |
| Power Loss NO [W] | 10626 | |
| Continuous Current (NO) [A] | 480 | |
| Intermittent Current (NO) [A] | 528 | |
| Continuous Current (NO) [A] | 443 | |
| Intermittent Current (NO) [A] | 487 |
Technical data
| Motor power | 250 kW / 350 HP | |
| Mains voltage | 380 - 480 VAC | |
| Phase | Three-phase | |
| Protection rating | IP21/Type 1+mains shield | |
| Frame size | D2n | |
| RFI filter | Class A2 (EMC C3) | |
| Brake chopper | No | |
| Safe Torque Off | Yes | |
| Control panel | Graphical LCP | |
| PCB coating | Coated PCB | |
| Mains option | Mains Disconnect + Fuse | |
| Fieldbus | PROFINET MCA 120 | |
| Product type | Frequency converter | |
| Continuous output current | 480 A | |
| Continuous current (high line) | 443 A | |
| Intermittent output current | 528 A | |
| Apparent power | 333 kVA | |
| Power loss | 11371 W | |
| Power, normal overload | 250 kW | |
| Height | 1780 mm | |
| Width | 1020 mm | |
| Depth | 380 mm | |
| Depth with A/B options | 380 mm | |
| Packed volume | 0 L | |
| EAN | 5715253266398 | |
| ECCN (EU) | X.A.I.003 | |
| ECCN (US) | 3A999 | |
Documents
Operating guides, design guides, certificates and CAD drawings for 137G0734 are available on request. Ask for documents →
Other 250 kW / 350 HP variants in VLT HVAC Drive FC 102
- 134N5999 IP20 · Class A2 · D4H
- 136X4777 IP20 · Class A2 · D4H
- 136G0273 IP20 · Class A2 · D4H
- 134L4835 IP20 · Class A2 · D4H
- 134N1701 IP20 · Class A2 · D4H
- 134N1049 IP20 · Class A2 · D4H
- 134U3478 IP20 · Class A2 · D4H
- 134X1846 IP20 · Class A2 · D4H
- 134L6247 IP20 · Class A2 · D4H
- 134L3704 IP20 · Class A1 · D4H
- 167F1756 IP20 · Class A1 · D4H
- 136L9632 IP20 · Class A1 · D4H
- 136F9818 IP20 · Class A1 · D4H
- 134H8740 IP20 · Class A1 · D4H
- 135X4549 IP20 · Class A1 · D4H
- 134U1670 IP20 · Class A2 · D4H
- 134N9580 IP20 · Class A2 · D4H
- 137G6912 IP20 · Class A2 · D4H
- 134N9529 IP20 · Class A2 · D4H
- 134U1501 IP20 · Class A2 · D4H
- 134U0900 IP20 · Class A2 · D4H
- 134U0899 IP20 · Class A2 · D4H
- 134L4729 IP20 · Class A2 · D4H
- 136F8222 IP20 · Class A2 · D4H