Danfoss VLT HVAC Drive FC 102 FC-102P500T4E54N2TGC7XXSXXXXANB2CXXXXD0
137G2865

Danfoss 137G2865 - VLT HVAC Drive FC 102 (500 kW / 650 HP, IP54, 380-480V)

  • Frequency Converter
  • VLT® HVAC Drive FC-102
  • (P500) 500 KW / 650 HP, Three phase
  • 380 - 480 VAC, (E54) IP54 / Type 12
  • LHD - AAF006 filter + A2 RFI
  • Safe Stop
  • Graphical Loc. Cont. Panel
  • Coated PCB, Fuse
  • Latest release std. SW.
  • Frame: F18
  • No C1 option, MCB-107 24V DC backup
  • EtherNet/IP MCA 121, MCB-112 PTC Therm. Card
  • ATEX: II (2) G [Ex eb Gb] [Exdb Gb] / II (2) D [Ex tb Db]
Model code:
FC-102P500T4E54N2TGC7XXSXXXXANB2CXXXXD0
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® HVAC Drive FC-
Series102
Power RatingP500(P500) 500 KW / 650 HP
PhaseTThree phase
Mains Voltage4380 - 480 VAC
EnclosureE54(E54) IP54 / Type 12
RFI FilterN2LHD - AAF006 filter + A2 RFI
Brake - Safe StopTSafe Stop
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains Option7Fuse
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionANEtherNet/IP MCA 121
B OptionB2MCB-112 PTC Therm. Card
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionD0MCB-107 24V DC backup
Frame SizeF18
Power 110% (NO) [KW]500
Height [mm]2277,0
Width w/ no C options [mm]2802,0
Depth [mm]607,0
Depth with Option A/B [mm]607,0
kVA610
Power Loss NO [W]21909
Power Loss NO [W]19896
Continuous Current (NO) [A]880
Intermittent Current (NO) [A]968
Continuous Current (NO) [A]780
Intermittent Current (NO) [A]858
ATEX Marking 1ATEX: II (2) G [Ex eb Gb] [Ex
ATEX Marking 2db Gb] / II (2) D [Ex tb Db]

Technical data

Motor power500 kW / 650 HP
Mains voltage380 - 480 VAC
PhaseThree-phase
Protection ratingIP54 / Type 12
Frame sizeF18
RFI filterClass A2 (EMC C3)
Brake chopperNo
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionIntegrated Fuse
FieldbusEtherNet/IP MCA 121
Product typeFrequency converter
Continuous output current880 A
Continuous current (high line)780 A
Intermittent output current968 A
Apparent power610 kVA
Power loss21909 W
Power, normal overload500 kW
Height2277 mm
Width2802 mm
Depth607 mm
Depth with A/B options607 mm
Net weight1899 kg
Gross weight1899.3 kg
Packed volume0 L
EAN5715253288291
ECCN (EU)X.A.I.003
ECCN (US)3A999

Documents

Operating guides, design guides, certificates and CAD drawings for 137G2865 are available on request. Ask for documents →

Other 500 kW / 650 HP variants in VLT HVAC Drive FC 102

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery