Danfoss VLT AutomationDrive FC 302 FC-302P37KT7P21H2BGCXXXS067XALBXCXXXXDX
137G8955

Danfoss 137G8955 - VLT AutomationDrive FC 302 (37 kW / 50 HP, IP21, 525-690V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P37K) 37 KW / 50 HP, Specific Ratings: 30kW@525-550V, 40HP@575V, 37kW@690V
  • Three phase, 525 - 690 VAC *,IP21 / Type 1 Backplate
  • RFI Filter
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Coated PCB, No Mains Option
  • (S067)Integrated MotionControl
  • Frame: C2
  • PROFINET MCA 120, No B Option
  • No C1 option, No D option
Model code:
FC-302P37KT7P21H2BGCXXXS067XALBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP37K(P37K) 37 KW / 50 HP
PhaseTThree phase
Mains Voltage7525 - 690 VAC *
EnclosureP21IP21 / Type 1 Backplate
RFI FilterH2RFI Filter
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBCCoated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseS067(S067)Integrated MotionControl
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC2
Power 150% (HO) [KW]37
Power 110% (NO) [KW]45
Height [mm]780,0
Width w/ no C options [mm]370,0
Depth [mm]332,0
Depth with Option A/B [mm]332,0
kVA49
Power Loss NO [W]900
Power Loss HO [W]740
Continuous Current (NO) [A]54
Intermittent Current (NO) [A]59.4
Continuous Current (NO) [A]52
Intermittent Current (NO) [A]57.2
Continuous Current (HO) [A]43
Intermittent Current (HO) [A]64.5
Continuous Current (HO) [A]41
Intermittent Current (HO) [A]61.5
Power Rating at 525-550V30kW
Power Rating at 575V40HP
Power Rating at 690V37kW

Technical data

Motor power37 kW / 50 HP
Mains voltage525 - 690 VAC *
PhaseThree-phase
Protection ratingIP21 / Type 1 Backplate
Frame sizeC2
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingCoated PCB
Mains optionNone
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current54 A
Continuous current (high line)52 A
Intermittent output current59.4 A
Continuous current (high overload)43 A
Apparent power49 kVA
Power loss900 W
Power, normal overload45 kW
Power, high overload37 kW
Height780 mm
Width370 mm
Depth332 mm
Depth with A/B options332 mm
Net weight56.18 kg
Gross weight58.02 kg
Packed volume228.1 L
EAN5715253353128
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137G8955 are available on request. Ask for documents →

Other 37 kW / 50 HP variants in VLT AutomationDrive FC 302

Request a quote

Price and delivery time, usually within one business day.