137H0936
Danfoss 137H0936 - VLT Refrigeration Drive FC 103 (355 kW / 500 HP, IP20, 380-480V)
- Frequency converter
- VLT® Refrigeration Drive FC-103
- (N355) 355 KW / 500 HP,
- Three phase, 380 - 480 VAC,(E20) IP20 / Chassis
- RFI filter Class A2
- Safe Stop
- Graphical Loc. Cont. Panel
- Coated PCB, Fuse
- Latest release std. SW.
- PROFINET MCA 120, No B Option
- No C1 option, No D option
- Frame: E3H
Model code:
FC-103N355T4E20H2TGC7XXSXXXXALBXCXXXXDX
FC-103N355T4E20H2TGC7XXSXXXXALBXCXXXXDX
Similar products
- Genuine Danfoss products
- Danfoss manufacturer warranty
- Reply within one business day
Product details
| Product Group | FC- | VLT® Refrigeration Drive |
| Series | 103 | |
| Power Rating | N355 | (N355) 355 KW / 500 HP |
| Phase | T | Three phase |
| Mains Voltage | 4 | 380 - 480 VAC |
| Enclosure | E20 | (E20) IP20 / Chassis |
| RFI Filter | H2 | RFI filter Class A2 |
| Brake - Safe Stop | T | Safe Stop |
| LCP | G | Graphical Loc. Cont. Panel |
| Coating PCB | C | Coated PCB |
| Mains Option | 7 | Fuse |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| A Option | AL | PROFINET MCA 120 |
| B Option | BX | No B Option |
| C0 Option MCO | CX | No C0 option |
| C1 Option | X | No C1 option |
| C Option Software | XX | No software option |
| D Option | DX | No D option |
| Frame Size | E3H | |
| Power 110% (NO) [KW] | 355 | |
| Height [mm] | 1578,0 | |
| Width w/ no C options [mm] | 507,0 | |
| Depth [mm] | 482,0 | |
| Depth with Option A/B [mm] | 482,0 | |
| kVA | 456 | |
| Power Loss NO [W] | 6928 | |
| Power Loss NO [W] | 5910 | |
| Continuous Current (NO) [A] | 658 | |
| Intermittent Current (NO) [A] | 724 | |
| Continuous Current (NO) [A] | 590 | |
| Intermittent Current (NO) [A] | 649 |
Technical data
| Motor power | 355 kW / 500 HP | |
| Mains voltage | 380 - 480 VAC | |
| Phase | Three-phase | |
| Protection rating | IP20 / Chassis | |
| Frame size | E3H | |
| RFI filter | Class A2 (EMC C3) | |
| Brake chopper | No | |
| Safe Torque Off | Yes | |
| Control panel | Graphical LCP | |
| PCB coating | Coated PCB | |
| Mains option | Integrated Fuse | |
| Fieldbus | PROFINET MCA 120 | |
| Product type | Frequency converter | |
| Continuous output current | 658 A | |
| Continuous current (high line) | 590 A | |
| Intermittent output current | 724 A | |
| Apparent power | 456 kVA | |
| Power loss | 6928 W | |
| Power, normal overload | 355 kW | |
| Height | 1578 mm | |
| Width | 507 mm | |
| Depth | 482 mm | |
| Depth with A/B options | 482 mm | |
| Net weight | 272 kg | |
| Gross weight | 272.3 kg | |
| EAN | 5715253374611 | |
| ECCN (EU) | Y901 | |
| ECCN (US) | 3A999.a | |
Documents
Operating guides, design guides, certificates and CAD drawings for 137H0936 are available on request. Ask for documents →
Other 355 kW / 500 HP variants in VLT Refrigeration Drive FC 103
- 136H6721 IP00 · Class A1 · E3H
- 136N0200 IP20 · Class A2 · E3H
- 136X0780 IP20 · Class A2 · E3H
- 132H9698 IP20 · Class A2 · E3H
- 132L0940 IP20 · Class A2 · E3H
- 137H0566 IP20 · Class A2 · E3H
- 132N5473 IP20 · Class A2 · E3H
- 136H2829 IP20 · Class A2 · E3H
- 132X1909 IP20 · Class A2 · E3H
- 135X4497 IP20 · Class A2 · E3H
- 137L4530 IP20 · Class A2 · E3H
- 135U8526 IP20 · Class A2 · E3H
- 132X7171 IP20 · Class A2 · E3H
- 136F1868 IP20 · Class A2 · E3H
- 132N7875 IP20 · Class A2 · E3H
- 132X4915 IP20 · Class A2 · E3H
- 132X2692 IP20 · Class A2 · E3H
- 167G5545 IP20 · Class A2 · E3H
- 137X8511 IP20 · Class A2 · E3H
- 167F1043 IP20 · Class A2 · E3H
- 132N5348 IP20 · Class A2 · E3H
- 135U6670 IP20 · Class A2 · E3H
- 167F4068 IP20 · Class A2 · E3H
- 137N0682 IP20 · Class A2 · E3H