Danfoss VACON NXP Common DC Bus NXA01685-A0T02SO-A1AFB20000+FL25+LS60+GSSE+DLES
137H1399

Danfoss 137H1399 - VACON NXP Common DC Bus (114 kW, IP00, 380-500V)

  • Vacon Active Front-End Unit
  • 380 – 500 Vac (465-800 Vdc), 168 Amp,IP00
  • Alpha-numeric display
  • IEC61800-3 for IT networks
  • No Brake
  • A Slot: 6DI,DO,2AI,1AO,+10Vr,+24V
  • B Slot: STO, ATEX therm
  • C Slot: 1RO(NO/NC),1RO(NO),therm
  • D Slot: No board
  • E Slot: No board
  • Manual: Spanish
  • Frame 09 INU
  • ATEX: II (2) GD
Model code:
NXA01685-A0T02SO-A1AFB20000+FL25+LS60+GSSE+DLES
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupNXAActive Front-End Unit
Customized Drive+BM26Vacon Dark Grey NXP
Mechanical ModificationSStandard air cooled drive
Mains voltage5-380 – 500 Vac (465-800 Vdc)
Current0168168 Amp
Control KeypadAAlpha-numeric display
Enclosure0IP00
EMC emission levelsTIEC61800-3 for IT networks
Brake Chopper0No Brake
Electrical Modification2AFE module w/o LCL
Card ModificationsO-IP54 ContUnit, varn/fib conn.
Shipping Package+GSSESea container package
Warranty+WT01Warranty 12/18 months
Gland Plate Option+QGNONo conduit plate
Option Slot AA16DI,DO,2AI,1AO,+10Vr,+24V
Option Slot BAFSTO, ATEX therm
Option Slot CB21RO(NO/NC),1RO(NO),therm
Option Slot D00No board
Option Slot E00No board
Firmware language package+FL25US,FR,ES,PT;Americas
Documentation Level+DPAPPaper manuals
Documentation Lang. Preference+DLESSpanish
System Firmware+FNP02System software NXP
Software licenseNONEno software license
Application+ARFIFF02AFE application NXA,NXI,NXP
Parameter SetNONEnone
Motor Parameter Default+LS60Default Motor frequency 60HZ
Labeling options+LPC1no additional labels
CE Approval+GACECE Approval
UL Approval+GAULUL approval
RCM Approval+GACTRCM Approval N16307
Marine approvalNONEno marine approval
KC Approval+GAKCKorean Approval
Ukrainian Approval+GAUAUkrainian Approval
EAC Approval+GAEAEAC Approval
Frame SizeFI09Frame 09 INU
Motor Power Low Overload [kW]114
Motor Power High Overload [kW]-
Dimensions WxHxD [mm]239X1030X372
Continuous Current (NO) [A]170
Continuous Current (HO) [A]140
ATEX Marking 1ATEX: II (2) GD

Technical data

Motor power114 kW
Mains voltage380 – 500 Vac (465-800 Vdc)
PhaseThree-phase
Protection ratingIP00
Frame sizeFI09
RFI filterNone (EMC C4)
Brake chopperNo
Control panelAlphanumeric Keypad
Product typeActive Front-End Unit
Continuous output current170 A
Continuous current (high overload)140 A
Rated current168 A
Power, low overload114 kW
Standard I/O6DI,DO,2AI,1AO,+10Vr,+24V
Height1030 mm
Width239 mm
Depth372 mm
Net weight67 kg
Gross weight68 kg
EAN5715253379326
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137H1399 are available on request. Ask for documents →

Other 114 kW variants in VACON NXP Common DC Bus

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty · Worldwide delivery

We only use your details to answer this request. See our privacy policy.