Danfoss VLT AutomationDrive FC 302 FC-302P30KT5E66H2BGXXXXS067XALB6CXXXXDX
137H9690

Danfoss 137H9690 - VLT AutomationDrive FC 302 (30 kW / 40 HP, IP66, 380-500V)

  • Frequency converter
  • VLT® AutomationDrive FC-302
  • (P30K) 30 KW / 40 HP,
  • Three phase, 380 - 500 VAC,(E66) IP66 / NEMA 4X
  • RFI Filter
  • Brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • (S067)Integrated MotionControl
  • Frame: C1
  • PROFINET MCA 120, MCB-150 Safe Option TTL
  • No C1 option, No D option
Model code:
FC-302P30KT5E66H2BGXXXXS067XALB6CXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AutomationDrive FC-
Series302
Power RatingP30K(P30K) 30 KW / 40 HP
PhaseTThree phase
Mains Voltage5380 - 500 VAC
EnclosureE66(E66) IP66 / NEMA 4X
RFI FilterH2RFI Filter
Brake - Safe StopBBrake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AXStandard Cable Entries
Adaptation BXNo adaptation
Software ReleaseS067(S067)Integrated MotionControl
Software Language PackXStandard Language Pack
A OptionALPROFINET MCA 120
B OptionB6MCB-150 Safe Option TTL
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeC1
Power 150% (HO) [KW]30
Power 110% (NO) [KW]37
Height [mm]685,0
Width w/ no C options [mm]308,0
Depth [mm]311,0
Depth with Option A/B [mm]311,0
kVA42.3
Power Loss NO [W]698
Power Loss HO [W]570
Continuous Current (NO) [A]73
Intermittent Current (NO) [A]80.3
Continuous Current (NO) [A]65
Intermittent Current (NO) [A]71.5
Continuous Current (HO) [A]61
Intermittent Current (HO) [A]91.5
Continuous Current (HO) [A]52
Intermittent Current (HO) [A]78

Technical data

Motor power30 kW / 40 HP
Mains voltage380 - 500 VAC
PhaseThree-phase
Protection ratingIP66 / NEMA 4X
Frame sizeC1
RFI filterClass A2 (EMC C3)
Brake chopperYes
Safe Torque OffYes
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
FieldbusPROFINET MCA 120
Product typeFrequency converter
Continuous output current73 A
Continuous current (high line)65 A
Intermittent output current80.3 A
Continuous current (high overload)61 A
Apparent power42.3 kVA
Power loss698 W
Power, normal overload37 kW
Power, high overload30 kW
Height685 mm
Width308 mm
Depth311 mm
Depth with A/B options311 mm
Net weight38.71 kg
Gross weight40.21 kg
EAN5715253466804
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137H9690 are available on request. Ask for documents →