Danfoss VLT AQUA Drive FC 202 FC-202P1K1T6E55HXXGXXOXSXXXXAXBXCXXXXDX
137L4886

Danfoss 137L4886 - VLT AQUA Drive FC 202 (1.1 kW / 1.5 HP, IP55, 525-600V)

  • Frequency converter
  • VLT® AQUA Drive FC-202
  • (P1K1) 1.1 KW / 1.5 HP,
  • Three phase, 525 - 600 VAC,IP55 / Type 12
  • No RFI Filter
  • No brake chopper
  • Graphical Loc. Cont. Panel
  • Not coated PCB, No Mains Option
  • Latest release std. SW.
  • Frame: A5
  • No A Option, No B Option
  • No C1 option, No D option
Model code:
FC-202P1K1T6E55HXXGXXOXSXXXXAXBXCXXXXDX
Similar products
  • Genuine Danfoss products
  • Danfoss manufacturer warranty
  • Reply within one business day

Product details

Product GroupFC-VLT® AQUA Drive FC-
Series202
Power RatingP1K1(P1K1) 1.1 KW / 1.5 HP
PhaseTThree phase
Mains Voltage6525 - 600 VAC
EnclosureE55IP55 / Type 12
RFI FilterHXNo RFI Filter
Brake - Safe StopXNo brake chopper
LCPGGraphical Loc. Cont. Panel
Coating PCBXNot coated PCB
Mains OptionXNo Mains Option
Adaptation AOMetric thread cable entry
Adaptation BXNo adaptation
Software ReleaseSXXXLatest release std. SW.
Software Language PackXStandard Language Pack
A OptionAXNo A Option
B OptionBXNo B Option
C0 Option MCOCXNo C0 option
C1 OptionXNo C1 option
C Option SoftwareXXNo software option
D OptionDXNo D option
Frame SizeA5
Power 150% (HO) [KW]1.1
Power 110% (NO) [KW]1.1
Height [mm]420,0
Width w/ no C options [mm]242,0
Depth [mm]200,0
Depth with Option A/B [mm]200,0
kVA2.39
Power Loss NO [W]50
Power Loss HO [W]50
Continuous Current (NO) [A]2.6
Intermittent Current (NO) [A]2.86
Continuous Current (NO) [A]2.4
Intermittent Current (NO) [A]2.64
Continuous Current (HO) [A]2.6
Intermittent Current (HO) [A]3.9
Continuous Current (HO) [A]2.4
Intermittent Current (HO) [A]3.6

Technical data

Motor power1.1 kW / 1.5 HP
Mains voltage525 - 600 VAC
PhaseThree-phase
Protection ratingIP55 / Type 12
Frame sizeA5
RFI filterNone
Brake chopperNo
Control panelGraphical LCP
PCB coatingUncoated
Mains optionNone
FieldbusNone
Product typeFrequency converter
Continuous output current2.6 A
Continuous current (high line)2.4 A
Intermittent output current2.86 A
Continuous current (high overload)2.6 A
Apparent power2.39 kVA
Power loss50 W
Power, normal overload1.1 kW
Power, high overload1.1 kW
Height420 mm
Width242 mm
Depth200 mm
Depth with A/B options200 mm
Net weight11.79 kg
Gross weight12.41 kg
Packed volume52.4 L
EAN5715253523033
ECCN (EU)Y901
ECCN (US)3A999.a

Documents

Operating guides, design guides, certificates and CAD drawings for 137L4886 are available on request. Ask for documents →

Other 1.1 kW / 1.5 HP variants in VLT AQUA Drive FC 202

Request a quote

Price and delivery time, usually within one business day.

Genuine Danfoss · Manufacturer warranty

We only use your details to answer this request. See our privacy policy.